Main circuit terminals
 Cable gauge of main circuit terminals and earth (ground) terminals
Use an appropriate cable gauge to suppress the voltage drop to 2% or less.
If the wiring distance is long between the inverter and motor, the voltage drop in the main circuit will cause the motor torque to decrease especially at a low speed.
The following table indicates a selection example for the wiring length of 20 m.
 SLD rating (Pr.570 Multiple rating setting = "0")
• 600 V class (575 V input power supply)
Terminal
Applicable
screw
inverter model
size

FR-F860-00680
M8
FR-F860-01080
M8
FR-F860-01440
M10
FR-F860-01670
M10
FR-F860-02430
M10
FR-F860-02890
M12 (M10) 24.5
FR-F860-03360
M12 (M10) 24.5
FR-F860-04420
M12 (M10) 46

The cables used should be 75°C copper cables.

The terminal screw size indicates the size of terminal screw for R/L1, S/L2, T/L3, U, V, W, PR, P/+, N/-, P1, P3, and the screw for earthing (grounding), and P/+ for
option connection. A screw for earthing (grounding) of the FR-F860-02890 or higher is indicated in ( ).
 LD rating (Pr.570 Multiple rating setting = "1")
• 600 V class (575 V input power supply)
Terminal
Applicable
screw
inverter model
size

FR-F860-00680
M8
FR-F860-01080
M8
FR-F860-01440
M10
FR-F860-01670
M10
FR-F860-02430
M10
FR-F860-02890
M12 (M10) 24.5
FR-F860-03360
M12 (M10) 24.5
FR-F860-04420
M12 (M10) 46

The cables used should be 75°C copper cables.

The terminal screw size indicates the size of terminal screw for R/L1, S/L2, T/L3, U, V, W, PR, P/+, N/-, P1, P3, and the screw for earthing (grounding), and P/+ for
option connection. A screw for earthing (grounding) of the FR-F860-02890 or higher is indicated in ( ).
The line voltage drop can be calculated by the following formula:
Line voltage drop [V] =
wire resistance [mΩ/m]
×
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque reduction) in the low speed range.
NOTE
• Tighten the terminal screw to the specified torque. A screw that has been tightened too loosely can cause a short circuit or malfunction. A screw that has been
tightened too tightly can cause a short circuit or malfunction due to the unit breakage.
• Use crimp terminals with insulation sleeves to wire the power supply and motor.
8
WIRING
Crimp terminal
Tightening
torque
R/L1,
P/+,
N•m
S/L2,
U, V, W
P1
T/L3
7.8
22-8
22-8
22-8
7.8
38-8
38-8
38-8
14.7
60-10
60-10
60-10
14.7
60-10
60-10
60-10
14.7
80-10
80-10
80-10
100-12
100-12
100-12
125-12
125-12
125-12
2×80-12 2×80-12 2×80-12 60-10
Crimp terminal
Tightening
torque
R/L1,
N•m
P/+,
S/L2,
U, V, W
P1
T/L3
7.8
22-8
22-8
22-8
7.8
38-8
38-8
38-8
14.7
60-10
60-10
60-10
14.7
60-10
60-10
60-10
14.7
80-10
80-10
80-10
100-12
100-12
100-12
125-12
125-12
125-12
2×80-12 2×80-12 2×80-12 60-10
wiring distance [m]
×
HIV cables, etc. (mm
Earthing
R/L1,
P/+,
(grounding)
S/L2,
U, V, W
P1
cable
T/L3
22-8
22
22
22
22-8
38
38
38
38-10
60
60
60
38-10
60
60
60
38-10
80
80
80
38-10
100
100
100
38-10
125
125
125
2×80
2×80
2×80
HIV cables, etc. (mm
Earthing
R/L1,
P/+,
(grounding)
S/L2,
U, V, W
P1
cable
T/L3
22-8
22
22
22
22-8
38
38
38
38-10
60
60
60
38-10
60
60
60
38-10
80
80
80
38-10
100
100
100
38-10
125
125
125
2×80
2×80
2×80
current [A] / 1000
×
Cable gauge

2
AWG/MCM
)
Earthing
R/L1,
P/+,
(grounding)
S/L2,
U, V, W
P1
cable
T/L3
22
4
4
2
22
1
1
1/0
38
1/0
1/0
1/0
38
2/0
2/0
2/0
38
4/0
250
4/0
38
250
300
250
38
2×2/0
2×2/0
2×2/0
60
2×4/0
2×250
2×4/0
Cable gauge

2
AWG/MCM
)
Earthing
R/L1,
P/+,
(grounding)
S/L2,
U, V, W
P1
cable
T/L3
22
4
4
2
22
2
2
1/0
38
1/0
1/0
1/0
38
2/0
2/0
2/0
38
4/0
250
4/0
38
250
300
250
38
2×2/0
2×3/0
2×2/0
60
2×4/0
2×250
2×4/0
Earthing
(grounding)
cable
4
4
1
1
1
1
1
1/0
Earthing
(grounding)
cable
4
4
1
1
1
1
1
1/0