Auxiliary circuit current consumption

Auxiliary circuit current consumption varies depending on the actual drive configuration and
options. Contact ABB for the delivery-specific value.

Energy efficiency data (EU ecodesign)

Energy efficiency data is not provided for the drive/unit. The multidrives are not in the scope
of the EU ecodesign requirements (Regulation EU/2019/1781) or the UK ecodesign
requirements (Regulation SI 2021 No. 745).

Protection classes

Degrees of protection
(IEC/EN 60529)
Enclosure types (UL50)
Overvoltage category
(IEC/EN 60664-1)
Protective class
(IEC/EN 61800-5-1)

Ambient conditions

Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Installation site altitude
Air temperature
Relative humidity
IP42 (standard), IP54 (option +B055)
UL Type 1 (standard), UL Type 12 (option +B055). For indoor use only.
III, except for auxiliary power connections (fan, control, heating, lighting, cooling
unit pump etc) which are category II.
I
Operation
installed for stationary
use
0...2000 m (0...6562 ft)
above sea level. For alti-
tudes over 2000 m, contact
ABB.
Output derated above 1000
m (3281 ft).
0 ... +45 °C
(+32 ... +113 °F), no con-
densation allowed. Output
derated in the range
+45 ... +55 °C
(+113 ... +131 °F).
Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the presence
Storage
in the protective package
-
-40 to +70 °C (-
40 to +158 °F)
Max. 95%
of corrosive gases.
Technical data 59
Transportation
in the protective package
-
-40 to +70 °C (-
40 to +158 °F)
Max. 95%