LG MASTER-K200S Series User Manual page 8

Programmable logic controller
Hide thumbs Also See for MASTER-K200S Series:
Table of Contents

Advertisement

Chapter 1. INTRODUCION
Digital/analog conversion module allows digital value of the CPU to be converted into an analog value
and to be output externally. Digital input value of 0 leads to analog output value of 0V and 4000 leads
to 10V. Digital input value of 1 is equal to 2.5mV.
2) Voltage output - G4F-DA3V/G4F-DA2V/G6F-DA2V
10V
0V
-10V
0
Digital/analog conversion module allows digital value of the CPU to be converted into an analog value
and to be output externally. Digital input value of 0 leads to analog output value of -10V and 4000 leads
to10V. Digital input value of 1 is equal to 5mV.
3) Current output – G3F-DA3I/G4F-DA3I/G4F-DA2I/G6F-DA2I
20 ㎃
12 ㎃
4 ㎃
0
On current output, digital value of 0 is to be converted into 4mA and 4000 into 20mA. Digital input of 1 is
equal to 4 ㎂.
2000
4000
Digital Input Value
[Fig 1.6] D/A conversion characteristics(Voltage output)
2000
4000
Digital Input Value
[Fig 1.7] D/A conversion characteristics(Current output)
1 - 3
5 ㎷
0.005V
0V
2000
2001 2002 2003
Digital Input
4 ㎂
12.004 ㎃
12.000 ㎃
2000
2001
2002 2003
2004
Digital Input
2004
2005
2005