Advertisement

Floor Standing
Cooling Only (R410A,50/60Hz)
6CSP0-04A (Replace : 6CSP0-03C)
P/No.: MFL60778813

Advertisement

Table of Contents
loading

Summary of Contents for LG AP-Q36GRA0

  • Page 1 Floor Standing Cooling Only (R410A,50/60Hz) 6CSP0-04A (Replace : 6CSP0-03C) P/No.: MFL60778813...
  • Page 2 This is our environment-friendly policy to protect the environment for the future. LG’s "Floor Standing" is the indoor unit which is used as luxury domestic or commercial appliance and is used in the places like restaurant, store or meeting room.
  • Page 3: Floor Standing

    Floor Standing 1. Models List 2. Model Number Nomenclature 3. List of Functions 4. Specifications 5. Dimensions 6. Piping Diagrams 7. Wiring Diagrams 8. Capacity Tables 9. The Coefficient of Capacity Change 10. Air flow and temperature distributions (reference data) 11.
  • Page 4: Models List

    1.1 Cooling Only n 0 Series Nominal Capacity Rated Capacity Power Supply Class_Rated Refrigerant Model Name (kW) (V, Ø, Hz) (kBtu/h) AP-Q36GRA0 10.5 220-240, 1, 50 220, 1, 60 14.1 AP-Q48GTA0 R410A 380-415, 3, 50 28.7 AP-Q100LFA0 380, 3, 60...
  • Page 5: Model Number Nomenclature

    Floor Standing 2. Model Number Nomenclature n 0 Series A P - Q G R A 0 Development Sequence Function A : Basic Chassis Type Electric Standard (Volts / Freq. / Phase) G : 220-240V, 1Ø, 50Hz / 220V, 1Ø, 60Hz L : 380-415V, 3Ø, 50Hz / 380V, 3Ø, 60Hz Nominal Cooling Capacity(Rated) Ex) 36 ➝...
  • Page 6: List Of Functions

    Floor Standing 3. List of Functions 3.1 Indoor Units Category Functions APNQ36GRA0 APNQ48GTA0 Air supply outlet Airflow direction control (left & right) Auto Auto Airflow direction control (up & down) Auto Auto Auto swing (left & right) Air flow Auto swing (up & down) Airflow steps (fan/cool/heat) 4 / 4 / - 4 / 4 / -...
  • Page 7 Floor Standing 3. List of Functions Category Functions APNQ60GT3E4 APNQ100LFA0 Air supply outlet Airflow direction control (left & right) Auto Manual Airflow direction control (up & down) Auto Manual Auto swing (left & right) Air flow Auto swing (up & down) Airflow steps (fan/cool/heat) 4 / 4 / - 2 / 3 / -...
  • Page 8: Outdoor Units

    Floor Standing 3. List of Functions 3.2 Outdoor Units Category Functions APUQ36GRA0 APUQ48GTA0 APUQ60GT3E4 APUQ100LFA0 Defrost / Deicing High pressure switch Low pressure switch Phase protection Reliability Restart delay (3-minutes) Self diagnosis Soft start Test function Convenience Night Silent Operation CAC network function Network soluation(LGAP) APUQ36GRA0 / APUQ48GTA0 /...
  • Page 9: Specifications

    Floor Standing 4. Specifications 4.1 Indoor Units Model Name APNQ36GRA0 APNQ48GTA0 V, Ø, Hz 220-240, 1, 50 220-240, 1, 50 Power Supply 220, 1, 60 220, 1, 60 Power Input (Indoor Unit only) Rated Running Current (Indoor Unit only) 0.50 0.91 Casing Color Middle White...
  • Page 10 Floor Standing 4. Specifications Model Name APNQ60GT3E4 APNQ100LFA0 220-240, 1, 50 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 220, 1, 60 Power Input (Indoor Unit only) Rated Running Current (Indoor Unit only) 0.91 Casing Color White Middle White W x H x D 590 x 1,840 x 440...
  • Page 11 Floor Standing 4. Specifications 4.2 Outdoor Units Model Name APUQ36GRA0 APUQ48GTA0 Min.~Rated 5.57 ~ 10.5 5.13 ~ 14.1 Cooling Min.~Rated Btu/h 19,000 ~ 36,000 17,500 ~ 48,000 Capacity Min.~Rated Heating Min.~Rated Btu/h Cooling Rated 3.30 4.15 Power Input Heating Rated Cooling Rated 15.0...
  • Page 12 Floor Standing 4. Specifications Model Name APUQ60GT3E4 APUQ100LFA0 Min. ~ Rated. ~ Max. 4.50 ~ 14.1 ~ 16.69 14.3 ~ 28.7 ~ - Cooling Min. ~ Rated. ~ Max. Btu/h 15,356 ~ 48,000 ~ 57,000 49,000 ~ 98,000 ~ - Capacity Min.
  • Page 13 Floor Standing 5. Dimensions 5.1 Indoor Units 10 _ Floor Standing...
  • Page 14 Floor Standing 5. Dimensions Floor Standing _ 11...
  • Page 15 Floor Standing 5. Dimensions 12 _ Floor Standing...
  • Page 16 Floor Standing 5. Dimensions Floor Standing _ 13...
  • Page 17 Floor Standing 5. Dimensions 5.2 Outdoor Units 14 _ Floor Standing...
  • Page 18 Floor Standing 5. Dimensions Floor Standing _ 15...
  • Page 19 Floor Standing 5. Dimensions 16 _ Floor Standing...
  • Page 20 Floor Standing 5. Dimensions Floor Standing _ 17...
  • Page 21: Piping Diagrams

    Floor Standing 6. Piping Diagrams Models : AP-Q36GRA0 Outdoor Unit Indoor Unit Service Valve (Liquid) Flare E.E.V. Connection Flare Connection Service Valve (Gas) Accumulator Compressor Refrigerant flow Cooling Location Description PCB Connector Thermistor for indoor room temperature CN-ROOM/TH Thermistor for evaporator inlet temperature...
  • Page 22 Floor Standing 6. Piping Diagrams Models : AP-Q48GTA0 Outdoor Unit Indoor Unit Strainer Service Valve (Liquid) Flare E.E.V. Connection Flare Connection Service Valve (Gas) Accumulator Compressor Refrigerant flow Cooling Location Description PCB Connector Thermistor for indoor room temperature CN-ROOM/TH Thermistor for evaporator inlet temperature CN-EVA/TH Thermistor for evaporator outlet temperature CN-EVA/TH2...
  • Page 23 Floor Standing 6. Piping Diagrams Models : AP-Q60GT3E4 Outdoor Unit Indoor Unit Strainer Service Valve (Liquid) Flare E.E.V. Connection Flare Connection Pressure Service Valve Sensor (Gas) Accumulator Compressor Refrigerant flow Cooling Location Description PCB Connector Thermistor for indoor room temperature CN-ROOM/TH Thermistor for evaporator inlet temperature CN-EVA/TH...
  • Page 24 Floor Standing 6. Piping Diagrams Models : AP-Q100LFA0 Outdoor Unit Indoor Unit Service Valve (Liquid) Strainer Strainer Flare Strainer Electronic Connection Expansion Valve Flare Connection Pressure Service Valve Sensor (Gas) Accumulator Refrigerant flow Seperator Cooling Inverter Compressor Refrigerant Flow Cooling Location Description PCB Connector...
  • Page 25: Wiring Diagrams

    Floor Standing 7. Wiring Diagrams Models : AP-Q36GRA0 22 _ Floor Standing...
  • Page 26 Floor Standing 7. Wiring Diagrams Models : AP-Q48GTA0 Floor Standing _ 23...
  • Page 27 Floor Standing 7. Wiring Diagrams Models : AP-Q60GT3E4 24 _ Floor Standing...
  • Page 28 Floor Standing 7. Wiring Diagrams Models : AP-Q100LFA0 Floor Standing _ 25...
  • Page 29: Capacity Tables

    Floor Standing 8. Capacity Tables Models: AP-Q36GRA0 Outdoor Air Temperature (°CDB) Indoor Air Temperature °CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 10.30 7.71 1.82...
  • Page 30 Floor Standing 8. Capacity Tables Models: AP-Q100LFA0 Outdoor Air Temperature (°CDB) Indoor Air Temperature °CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 28.16 21.45 6.41 26.94 20.76 7.79 25.29 19.92 8.91 24.52 19.25 9.69 23.45 18.66 10.64 22.80 18.01 10.70 22.16 17.45 9.36 16.0 22.0 29.89 21.73 8.40 28.66 21.08 8.89 27.01 20.30 10.24 26.23 19.65 11.00 25.15 19.11 11.47 24.51 18.47 11.19 23.86 17.93 9.47 18.0...
  • Page 31 Floor Standing 9. The Coefficient of Capacity Change 1) Rate of change in capacity due to the pipe length Capacity coefficient factor for piping length Pipe length(m) Capacity class (kBtu/h, by Model name) 36 / 48 1.000 1.000 0.993 0.980 0.967 0.953 0.940...
  • Page 32 Floor Standing 10. Air flow and temperature distributions (reference data) Models: APNQ36GRA0 Discharge Angle : 90˚ Air velocity [m/s] 2.7m Temperature [°C] 2.7m Models: APNQ48GTA0 Discharge Angle : 90˚ Air velocity [m/s] 3.2m Temperature [°C] 3.2m Floor Standing _ 29...
  • Page 33 Floor Standing 10. Air flow and temperature distributions (reference data) Models: APNQ60GT3E4 Discharge Angle : 90˚ Air velocity [m/s] 2.7m Temperature [°C] 2.7m Models: APNQ100LFA0 Discharge Angle : 90˚ Air velocity [m/s] 3.2m Temperature [°C] 3.2m 30 _ Floor Standing...
  • Page 34: Operation Range

    Floor Standing 11. Operation Range 48(118) Continuous operation -10(14) 18(64) 32(90) Indoor Unit [°C(°F) DB] Floor Standing _ 31...
  • Page 35: Sound Pressure Level

    Floor Standing 12. Sound Levels 12.1 Indoor Units Notes : 1. Sound measured at each 1m away from the front and bottom of the unit 2. Operating condition - Power source : 220-240V, 50Hz / 220V, 60Hz - Cooling : Indoor temperature (27°C DB, 19°C WB), Outdoor temperature (35°C DB, 24°C WB) 3.
  • Page 36 Floor Standing 12. Sound Levels APNQ100LFA0 NC - 65 NC - 60 NC - 55 NC - 50 NC - 45 NC - 40 NC - 35 NC - 30 NC - 25 Approximate NC - 20 Hearing Threshold NC - 15 1000 2000 4000...
  • Page 37 Floor Standing 12. Sound Levels 12.2 Outdoor Units Notes: 1. Sound measured at 1m away from the center of the unit 2. Operating condition - Power source : 220-240V, 50Hz / 220V, 60Hz - Cooling : Indoor temperature (27°C DB, 19°C WB), Outdoor temperature (35°C DB, 24°C WB) 3.
  • Page 38 Floor Standing 12. Sound Levels APUQ100LFA0 NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 Approximate NC-20 Hearing Threshold NC-15 1000 2000 4000 8000 Octave Band Center Frequency (Hz) Floor Standing _ 35...
  • Page 39: Installation

    Floor Standing 13. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only. 13.1 Select the best location 13.1.1 Indoor Unit •...
  • Page 40 Floor Standing 13. Installation 13.1.2 Outdoor Unit • If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted. • There should not be any animals or plants which could be affected by hot air discharged. •...
  • Page 41 Floor Standing 13. Installation 13.2 Installation of Indoor unit and outdoor unit The Indoor Unit Installation Wall Core Drill 200mm 70mm 70mm 1. The mounting floor should be strong and solid INSIDE OUTSIDE enough to prevent it from vibration. Wall 2.
  • Page 42 75±7 N·m 3/4" 110±10 N·m Connecting wire The installation piping is connectable in several direc- Drain hose tions.(Refer to figure 1 and 2) Connection pipe <Figure 1> Putty or insulating material (produced locally) Backward Sideways Forward <AP-Q36GRA0> Floor Standing _ 39...
  • Page 43 Taping gum type sealer. gum type sealer. Drain hose <AP-Q36GRA0, AP-Q48GTA0, AP-Q60GT3E4> Plastic Plastic Plastic band band band Pipings Connecting cable Power supply cord •...
  • Page 44 Indoor unit Power cord terminal Outdoor unit Cord clamp Main power <AP-Q36GRA0, AP-Q48GTA0, AP-Q60GT3E4> Indoor Terminal Block Outdoor Terminal Block 1(L) 2(N) 1(L) 2(N) * Make sure the rubber bushes are Connecting cable Properly used in knock-out holes <AP-Q100LFA0>...
  • Page 45 Floor Standing 13. Installation The unit is completely wired internally at the factory according to general rule of electrical technology, but local rules, if they are required, should be complied with. 2. Power supply Voltage Power source must fulfill the following conditions: - The working voltage should be higher than Power source voltage 90% and lower than 110% of the rated voltage...
  • Page 46 3) Parallel with the sea wind direction is more corrosive condition. Right angle with the sea wind is recommend- ed to reduce damage from salty breeze. Sea wind Sea wind 4) Select a well-drained spot. 5) When installing the outdoor unit on the seashore or in such an ambient condition, contact your LG dealer. Floor Standing _ 43...
  • Page 47: Function Of Remote Control

    Floor Standing 14. Function of Remote Control Control Description panel Remote control operation lamp Power ON/OFF button : Operation will start when this button is pressed, and stop when the button is pressed again. Indoor fan speed button : To select the desired fan speed.
  • Page 48 Yeongdeungpo-gu, Seoul, Korea (07336) http://partner.lge.com Copyright © 2012-2019 LG Electronics The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance Inc. All Rights Reserved. and ISO14001 certificate for environmental management system. Printed in Korea October/2019 The specifications, designs, and information in this brochure are subject to change without notice.

This manual is also suitable for:

Ap-q48gta0Ap-q100lfa0Ap-q60gt3e4

Table of Contents