This is our environment-friendly policy to protect the environment for the future. LG’s "Floor Standing" is the indoor unit which is used as luxury domestic or commercial appliance and is used in the places like restaurant, store or meeting room.
Floor Standing 1. Models List 2. Model Number Nomenclature 3. List of Functions 4. Specifications 5. Dimensions 6. Piping Diagrams 7. Wiring Diagrams 8. Capacity Tables 9. The Coefficient of Capacity Change 10. Air flow and temperature distributions (reference data) 11.
Floor Standing 2. Model Number Nomenclature n 0 Series A P - Q G R A 0 Development Sequence Function A : Basic Chassis Type Electric Standard (Volts / Freq. / Phase) G : 220-240V, 1Ø, 50Hz / 220V, 1Ø, 60Hz L : 380-415V, 3Ø, 50Hz / 380V, 3Ø, 60Hz Nominal Cooling Capacity(Rated) Ex) 36 ➝...
Floor Standing 3. List of Functions 3.1 Indoor Units Category Functions APNQ36GRA0 APNQ48GTA0 Air supply outlet Airflow direction control (left & right) Auto Auto Airflow direction control (up & down) Auto Auto Auto swing (left & right) Air flow Auto swing (up & down) Airflow steps (fan/cool/heat) 4 / 4 / - 4 / 4 / -...
Page 7
Floor Standing 3. List of Functions Category Functions APNQ60GT3E4 APNQ100LFA0 Air supply outlet Airflow direction control (left & right) Auto Manual Airflow direction control (up & down) Auto Manual Auto swing (left & right) Air flow Auto swing (up & down) Airflow steps (fan/cool/heat) 4 / 4 / - 2 / 3 / -...
Floor Standing 4. Specifications 4.1 Indoor Units Model Name APNQ36GRA0 APNQ48GTA0 V, Ø, Hz 220-240, 1, 50 220-240, 1, 50 Power Supply 220, 1, 60 220, 1, 60 Power Input (Indoor Unit only) Rated Running Current (Indoor Unit only) 0.50 0.91 Casing Color Middle White...
Page 10
Floor Standing 4. Specifications Model Name APNQ60GT3E4 APNQ100LFA0 220-240, 1, 50 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 220, 1, 60 Power Input (Indoor Unit only) Rated Running Current (Indoor Unit only) 0.91 Casing Color White Middle White W x H x D 590 x 1,840 x 440...
Floor Standing 8. Capacity Tables Models: AP-Q36GRA0 Outdoor Air Temperature (°CDB) Indoor Air Temperature °CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 10.30 7.71 1.82...
Page 30
Floor Standing 8. Capacity Tables Models: AP-Q100LFA0 Outdoor Air Temperature (°CDB) Indoor Air Temperature °CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 28.16 21.45 6.41 26.94 20.76 7.79 25.29 19.92 8.91 24.52 19.25 9.69 23.45 18.66 10.64 22.80 18.01 10.70 22.16 17.45 9.36 16.0 22.0 29.89 21.73 8.40 28.66 21.08 8.89 27.01 20.30 10.24 26.23 19.65 11.00 25.15 19.11 11.47 24.51 18.47 11.19 23.86 17.93 9.47 18.0...
Page 31
Floor Standing 9. The Coefficient of Capacity Change 1) Rate of change in capacity due to the pipe length Capacity coefficient factor for piping length Pipe length(m) Capacity class (kBtu/h, by Model name) 36 / 48 1.000 1.000 0.993 0.980 0.967 0.953 0.940...
Page 32
Floor Standing 10. Air flow and temperature distributions (reference data) Models: APNQ36GRA0 Discharge Angle : 90˚ Air velocity [m/s] 2.7m Temperature [°C] 2.7m Models: APNQ48GTA0 Discharge Angle : 90˚ Air velocity [m/s] 3.2m Temperature [°C] 3.2m Floor Standing _ 29...
Page 33
Floor Standing 10. Air flow and temperature distributions (reference data) Models: APNQ60GT3E4 Discharge Angle : 90˚ Air velocity [m/s] 2.7m Temperature [°C] 2.7m Models: APNQ100LFA0 Discharge Angle : 90˚ Air velocity [m/s] 3.2m Temperature [°C] 3.2m 30 _ Floor Standing...
Floor Standing 12. Sound Levels 12.1 Indoor Units Notes : 1. Sound measured at each 1m away from the front and bottom of the unit 2. Operating condition - Power source : 220-240V, 50Hz / 220V, 60Hz - Cooling : Indoor temperature (27°C DB, 19°C WB), Outdoor temperature (35°C DB, 24°C WB) 3.
Page 37
Floor Standing 12. Sound Levels 12.2 Outdoor Units Notes: 1. Sound measured at 1m away from the center of the unit 2. Operating condition - Power source : 220-240V, 50Hz / 220V, 60Hz - Cooling : Indoor temperature (27°C DB, 19°C WB), Outdoor temperature (35°C DB, 24°C WB) 3.
Floor Standing 13. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only. 13.1 Select the best location 13.1.1 Indoor Unit •...
Page 40
Floor Standing 13. Installation 13.1.2 Outdoor Unit • If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted. • There should not be any animals or plants which could be affected by hot air discharged. •...
Page 41
Floor Standing 13. Installation 13.2 Installation of Indoor unit and outdoor unit The Indoor Unit Installation Wall Core Drill 200mm 70mm 70mm 1. The mounting floor should be strong and solid INSIDE OUTSIDE enough to prevent it from vibration. Wall 2.
Page 42
75±7 N·m 3/4" 110±10 N·m Connecting wire The installation piping is connectable in several direc- Drain hose tions.(Refer to figure 1 and 2) Connection pipe <Figure 1> Putty or insulating material (produced locally) Backward Sideways Forward <AP-Q36GRA0> Floor Standing _ 39...
Page 43
Taping gum type sealer. gum type sealer. Drain hose <AP-Q36GRA0, AP-Q48GTA0, AP-Q60GT3E4> Plastic Plastic Plastic band band band Pipings Connecting cable Power supply cord •...
Page 44
Indoor unit Power cord terminal Outdoor unit Cord clamp Main power <AP-Q36GRA0, AP-Q48GTA0, AP-Q60GT3E4> Indoor Terminal Block Outdoor Terminal Block 1(L) 2(N) 1(L) 2(N) * Make sure the rubber bushes are Connecting cable Properly used in knock-out holes <AP-Q100LFA0>...
Page 45
Floor Standing 13. Installation The unit is completely wired internally at the factory according to general rule of electrical technology, but local rules, if they are required, should be complied with. 2. Power supply Voltage Power source must fulfill the following conditions: - The working voltage should be higher than Power source voltage 90% and lower than 110% of the rated voltage...
Page 46
3) Parallel with the sea wind direction is more corrosive condition. Right angle with the sea wind is recommend- ed to reduce damage from salty breeze. Sea wind Sea wind 4) Select a well-drained spot. 5) When installing the outdoor unit on the seashore or in such an ambient condition, contact your LG dealer. Floor Standing _ 43...
Floor Standing 14. Function of Remote Control Control Description panel Remote control operation lamp Power ON/OFF button : Operation will start when this button is pressed, and stop when the button is pressed again. Indoor fan speed button : To select the desired fan speed.