Download Print this page

Mitsubishi Electric Mr.SLIM PUZ-ZM35VKA-ET Service Manual page 103

Split-type, heat pump air conditioners

Advertisement

OPERATING PROCEDURE
12. Removing the compressor (MC)
(1) Remove the service panel. (See Photo 2)
(2) Remove the top panel. (See Photo 1)
(3) Remove the front panel. (See Photo 1)
(4) Remove the back panel. (See Photo 1)
(5) Remove the electrical parts box. (See Photo 5)
(6) Remove the thermistor <Discharge> (TH4) and thermistor
<Comp. surface> (TH33). (See Photo 8)
(7) Remove 3 separator fixing screws (4 × 10) and remove the
separator.
(8) Remove the compressor body felt and compressor shell
felt.
(9) Cutting the band and remove the rubber mount.
(10) Recover refrigerant.
(11) Remove 3 compressor fixing nuts by using a spanner or a
adjustable wrench.
(12) Remove the welded pipe of compressor inlet and outlet.
Note: Recover refrigerant without spreading it in the air.
13. Removing the power receiver
(1) Remove the service panel. (See Photo 2)
(2) Remove the top panel. (See Photo 1)
(3) Remove the front panel. (See Photo 1)
(4) Remove the back panel. (See Photo 1)
(5) Remove the electrical parts box. (See Photo 5)
(6) Recover refrigerant.
(7) Remove 4 welded pipes of power receiver inlet and outlet.
(8) Remove 2 receiver leg fixing screws (4 × 10).
(9) Remove the power receiver together with the receiver leg.
Note: Recover refrigerant without spreading it in the air.
OCH653C
PHOTOS/FIGURES
Photo 12
Compressor
shell felt
Compressor
(MC)
Compressor
body felt
Separator
Separator
fixing screw
Photo 13
Outlet
103
Rubber
mount
Band
Compressor
fixing nut
Inlet
Power
receiver
Valve bed
Receiver leg
fixing screw

Advertisement

loading