Mitsubishi Electric Mr.SLIM PUZ-ZM35VKA-ET Service Manual page 81

Split-type, heat pump air conditioners

Advertisement

SW2 setting
Discharge superheat on error occurring
SHd
0 to 255
ON
Cooling = TH4 or TH33−TH6
1
2 3 4 5 6
Heating = TH4 or TH33−TH5
Sub cool on error occurring SC
0 to 130
ON
Cooling = TH6−TH3
Heating = TH5−TH2
1
2 3 4 5 6
Thermo-on time until error stops
0 to 999
ON
1
2 3 4 5 6
Indoor pipe temperature/Liquid
(TH2 (3))
Indoor 3
ON
−39 to 88
1
2 3 4 5 6
Indoor pipe temperature/Cond./Eva. (TH5
(3))
Indoor 3
ON
−39 to 88
1
2 3 4 5 6
Indoor pipe temperature/Liquid (TH2 (4))
Indoor 4
−39 to 88
ON
1
2 3 4 5 6
Indoor pipe temperature/Cond./Eva
(TH5 (4))
Indoor 4
−39 to 88
ON
1
2 3 4 5 6
OCH653C
Display detail
81
The black square ( ) indicates a switch position.
Explanation for display
0 to 255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 150°C;
0.5 s
0 to 130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 115°C;
0.5 s
0 to 999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 s
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
When there is no indoor unit, "00" is displayed.
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
When there is no indoor unit, "00" is displayed.
0.5 s
2 s
1
50
0.5 s
2 s
1
15
0.5 s
2 s
4
15
Unit
°C
°C
Minute
°C
°C
°C
°C