Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before installation of (Mono bloc) Air-to-Water Heatpump system (hereafter referred to as “Mono bloc unit”). Electrical works and water installation works must be done by licensed electrician and licensed water system installer respectively.
Page 3
WARNING When installing electrical equipment at wooden building of metal lath or wire lath, in accordance with electrical facility standard, no electrical contact between equipment and building is allowed. Insulator must be installed in between. This installation may be subjected to building regulation approval applicable to respective country that may require to notify the local authority before installation.
Page 5
Item Unit Refrigerant System Fin material Aluminium (Pre Coat) Fin Type Corrugated Fin Heat Exchanger Row × Stage × FPI 2 × 51 × 18 Size (W × H × L) 903.7 × 1295.4 × 38.1 ø Single Power Source (Phase, Voltage, Cycle) Condition A35W7 A7W35...
Page 6
Item Unit Water System Performance Test Condition EN 14511 Cooling: 16 ~ 43 Outdoor Ambient °C Heating: -20 ~ 35 Operation Range Cooling: 5 ~ 20 Water Outlet °C Heating: 20 ~ 55 Cooling: 52.0 Internal Pressure Differential Heating: 88.0 Water Drain Hose Inner Diameter mm (inch) 15.0 (19/32)
Page 7
Features Inverter Technology - Energy saving High Efficiency Compact Design Environment Protection - Non-ozone depletion substances refrigerant (R410A) Easy to use control panel Weekly Timer setting Quality Improvement - Random auto restart after power failure for safety restart operation - Gas leakage protection - Prevent compressor reverse cycle - Inner protector to protect compressor...
Main Components CAUTION 240-250V DETAIL A Component name 1 PCB 9 Heater assem bly Connector name 0 Overload protector (3 pieces) Water inlet Single phase RCCB (Main Power) a Pressure relief valve Water outlet Single phase RCCB (Ba ckup Heater) 3 Heat Exchanger b Air purge valve c Water Filter Set...
6. Refrigeration and Water Cycle Diagram Outdoo r Side Mono bloc Unit Water Pressure Gauge Liquid Side Expansion (3-Way Valve) Strainer Valve Strainer Shut Shut Valve Valve Water Inlet Filter Water Pump Receiver Defrost Water Inlet Temp. Ref Pipe Temp. Sensor Temp.
Electronic Circuit Diagram Water System EXTERNAL COMP. SW HEAT/COOL SWITCH SG SIGNAL SOLAR TEMP. SENSOR DEMAND SIGNAL WATER TEMP. ZONE 1 WATER TEMP. ZONE 2 POOL TEMP. SENSOR BUFFER TANK SENSOR ROOM TEMP. ZONE 1 ROOM TEMP. ZONE 2...
Installation Instruction A place where the Mono bloc unit’s piping and Mono Bloc Unit wiring lengths come within reasonable ranges. If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed.
Disposal of Mono Bloc Unit Drain Water When a Drain elbow is used, please ensure to follow below: The unit should be placed on a stand which is taller than 50mm. Cover the 8 holes (ø20mm) with Rubber cap (refer to illustration below) Use a tray (field supply) when necessary to dispose the Mono bloc unit drain water.
Page 15
Recommended RCD 3 x min 4.0 mm 30mA, 2P, type A WH-MDC012H6E5 and WH-MDC016H6E5 3 x min 4.0 mm 30mA, 2P, type AC 2. To avoid the cable and cord being damaged by sharp edges, the cable and cord must be passed through the designated holes before being connected to the terminal block.
Page 16
Connecting Requirement For WH-MDC12H6E5 and WH-MDC16H6E5 This equipment’s power supply 1 complies with IEC/EN 61000-3-12 provided that the short circuit power S greater than or equal to 1100kW at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short circuit power S greater than...
Page 17
11 Tank OLP cable must be (2 x min 0.5 mm ), double insulation layer of PVC-sheathed or rubber-sheathed cable. • Power Supply 1 cord Apply cut • Power Supply 2 cord • Remote controller cable Optional cables: • External control cable •...
Page 18
Water sensor zone 1 and zone 2 cable shall be (2 x min 0.3 mm ), double insulation layer of PVC-sheathed or rubber-sheathed cable. 10 Demand signal cable shall be (2 x min 0.3 mm ), double insulation layer of PVC-sheathed or rubber- sheathed cable.
11.1.5 Installation of Remote Controller 11.1.5.1 Installation Location Install at the height of 1 to 1.5 m from the floor (Location where average room temperature can be detected). Install vertically against the wall. Avoid the following locations for installation. By the window, etc.
Page 20
For embedded type Preparation: Make 2 holes for screws using a driver. Mount the bottom case to the wall. Mount the top case. • Pass the wire through the hole • Align the claws of the top in the centre of the bottom case. case and then align the claws of the bottom case.
Page 21
Installation of Network Adaptor and Base Pan Heater 11.1.6.1 Network Adaptor and Installation (Optional) 1. Open the Cabinet front plate, then connect the 3. On the wall near the Mono bloc unit, attach the Network Adaptor Cable to the CN-CNT adaptor by screwing screws through the holes connector on the printed circuit board.
Reconfirmation Check RCCB Ensure the RCCB set to “ON” condition before check WARNING RCCB. Be sure to switch off all power supply before performing each of Turn on the power supply to the Mono bloc unit. the below checkings. Before obtaining access to terminals, all This testing could only be done when power is supply circuits must be disconnected.
Maintenance WARNING In order to ensure optimal performance of the unit, Do not add or replace other than R410A type. It may cause product damage, burst, injury and etc. Use compatible seasonal inspections on the unit, functional check R410A tools for refrigerant piping work and refrigerant of RCCB, field wiring and piping have to be charging during installation or servicing.
Page 24
Solar pump Outdoor air AW-A2W-TSOD (Total cable length shall be 30m or Pool pump sensor less) Pump Tank sensor Please use Panasonic specified part Boiler contact External control Connection of Optional PCB Tank sensor (CZ-NS4P) Room sensor Outdoor air sensor...
Insert the sensor into the sensor pocket and This section explains about the external devices paste it on the solar panel surface. (optional) recommended by Panasonic. Please always ensure to use the correct external device Dimensions (mm) during system installation.
Page 26
For optional pump. For optional mixing valve. Power supply: AC230V/50Hz, <500W Power supply: AC230V/50Hz (input open/output Recommended part: Yonos 25/6: made by Wilo close) Operating time: 30s~120s Recommended part: 167032: made by Caleffi...
Page 27
1) P-Q graph for different pump HEX duty 16kw rated duty 97 Max duty C5 12kw rated duty 81 Min duty 50 Water Flow Rate, Q (L/min) 12.2.2 Zone Water Pump Control Purpose: Water pump install at each zone to circulate the water inside each zone during buffer tank connection selected “YES”...
Page 28
WH-MDC16H6E5 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C 17.500 16.000 14.500 13.000 11.500 10.000 Outdoor Temperature (°C) 6.000 5.000 4.000 3.000 2.000...
Page 29
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C 16.000 14.000 12.000 10.000 8.000 6.000 Outdoor Temperature (°C) 6.000 5.000 4.000 3.000 2.000 1.000...
Page 30
Heating Capacity Table WH-MDC12H6E5 Water Out (°C) Input Input Input Input Capacity Input Capacity Capacity Capacity Capacity Outdoor Air (°C) Power Power Power Power Power (W) 9300 3460 8900 3620 8500 3790 8100 3950 7000 4100 10400 3370 10000 3660 9600 3950 9200...