Terminal compartment
Supplementary electron-
ics - Additional current
output
PBD-51041038
Fig. 17: Connection compartment - Ex-d-ia double chamber housing
1
Voltage supply, signal output
2
Ground terminal for connection of the cable screen
5.6

Supplementary electronics

To make a second measured value available for use, you can use the
supplementary electronics "Additional current output".
Both current outputs are passive and need a power supply.
Fig. 18: Terminal compartment, double chamber housing, supplementary elec-
tronics "Additional current output"
1
First current output (I) - Voltage supply and signal output, sensor (HART)
2
Additional current output (II) - Voltage supply and signal output (without
HART)
3
Ground terminal for connection of the cable screen
5.7

Switch-on phase

After connecting the instrument to power supply or after a voltage
recurrence, the instrument carries out a self-check for approx. 30 s:
Internal check of the electronics
Indication of the instrument type, hardware and software version,
measurement loop name on the display or PC
Indication of the status message "F 105 Determine measured
value" on the display or PC
The output signal jumps to the set fault current
SITRANS LG240 - Operating Instructions