Download Print this page

LG ABNW18GBHC0 Engineering Product Data Book page 35

Hide thumbs Also See for ABNW18GBHC0:

Advertisement

Compact
6. External pressure setting for
How to Set E.S.P. on the remote controller?
This is the function that decides the strength of the wind for each wind level and because this function is to make the instal-
lation easier.
• If you set ESP incorrectly, the air conditioner may malfunction.
• This setting must be carried out by a certificated-technician.
1
If pressing
seconds, it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
2
If entering into ESP setup mode by using
button, it indicates as the picture
below.
Select ESP fan step by
3
pressing
(01: very low, 02: low, 03:
medium, 04: high, 05:
very high)
• When setting ESP value on the product without very weak wind or power wind function, it may not work.
• Please be careful not to change the ESP value for each fan step.
• It does not work to setup ESP value for very low/power step for some products.
• ESP value is available for specific range belongs to the product.
10 _
Ceiling concealed duct - Middle static pressure(2)
Indoor unit
button long for 3
ESP step
Function Code
ESP value
button.
ESP value
Function code,
ESP code
Move to ESP value setting by pressing
4
button.
(It is 000 when delivering
from the warehouse.)
Press
button to setup ESP value.
5
(It is possible to setup ESP
value from 1 to 255, and 1 is
the smallest and 255 is the
biggest.)
Select ESP fan step again by using
6
button and setup ESP value, as No. 4
and 5, that corresponds each wind flow
Press
button to save.
7
Press
button to exit.
8
❈ After setup, it automatically gets out of
setup mode if there is no button input
for 25 seconds.
❈ When exiting without pressing set
button, the manipulated value is not
reflected.

Advertisement

loading

This manual is also suitable for:

Abnw24gbhc0Abnw30gm1a0Abnw36gm2a0