Trouble shooting guide
If you have installed and connected the unit as per the instructions listed earlier and it does not function correctly, use the
following table as a guide to fixing the problem. Look up the type of fault in the left column and check the possible causes
from the right column.
No.
Fault
1
LED lamp and indicator LED not lit
2
LED lamp not lit but red indicator LED is lit
3
LED lamp not lit but indicator LED is flashing green
4
LED lamp is lit but red indicator LED not lit
5
The LED lamp does not switch to emergency mode when the test
button is pressed
6
Indicator LED is constant green
7
Indicator LED not red after commissioning
8
The LED lamp works momentarily on emergency when the test
button is pressed or tested by command from the Nexus system
If the unit still does not work after checking these possible causes, contact ABB service in Australia on 1800 222 435,
Monday to Friday, 7.00am to 5.00pm (AEST) and ask for help. Our trained service personnel will usually be able to
take your call immediately and assist you in resolving your difficulty. ABB is committed to providing valuable through-life
support for its products.
ABB Australia Pty Limited
Phone: 1800 222 435
E-mail: AU-ABB-Stanilite@abb.com
www.stanilite.com.au
Possible causes
AC supply not connected; or
AC supply turned off; or
Test switch damaged
LED lamp damaged; or
LED lamp plug incorrectly inserted in the mother board
LED lamp damaged; or
LED lamp plug incorrectly inserted in the mother board
LED damaged; or
Check battery connection
Test switch damaged
Test switch damaged; or
Self check fail - return to factory
Check battery connection and battery plug polarity
Battery not yet be charged (allow up to 24 hours)
Copyright © 2016 ABB
All rights reserved
Installation manual
Exit LED edgelit surface mount
Standard, Nexus LX, Nexus RF
Doc no. 29-00074
Congratulations
Congratulations on choosing to use this ABB product covered by our unique through-life support system. This document
is designed to assist you during the installation of this product; for the safety of yourself and others ABB recommends
that you read this document thoroughly before commencing installation. The fittings are designed for easy
installation. They are advanced pieces of electronic equipment which, when treated with care and maintained through
regular and appropriate servicing, will perform reliably for many years to come.
Safety warning
In Australia and New Zealand, only licensed electricians are permitted by law to work with 240 volt electrical installations.
Do not attempt to install or connect this product unless you are a licensed electrician.
Turn off and isolate the electrical supply before connecting this fitting to the building wires.
Do not touch the terminals of the terminal block when the light fitting is energised.
The only user-serviceable parts are fluorescent or halogen lamp/s. LED light sources are not user-servicable.
Do not tamper with the fitting or the warranty will be void.
As the installer, it is your responsibility to ensure compliance with all relevant building and safety codes, (ie: AS3000,
AS/NZS2293). Refer to the applicable standards for data and mains cabling installation procedures and requirements.
Important note: This product is designed for indoor use only.
Nexus LX (data cable system)
The Nexus
range of emergency light fitting are designed to be connected together into a special communication network
®
over a Level 4 (or higher) high speed, single twisted pair data cable. The Nexus user and technical guide describes all
you need to know to successfully install a Nexus project. Ask for it from your supervisor, from your employer or from your
nearest ABB product supplier. The network cabling of the building must be installed as per the procedure detailed in the
Nexus user and technical guide. No mains or mains carrying cables are to be connected to the data terminals or cables.
Nexus RF (wireless system)
The Nexus RF range of light fittings are designed to communicate via a proprietary RF network, however the electrical
installation of the fittings is identical to that of a standard non-monitored fitting.
This document covers
What's inside the box
Safety warning
Surface mount base assembly
Installation instructions
Diffuser assembly
Removal instructions
Surface mount base cover
Testing precautions
Pictograph diffuser insert pack
Trouble shooting guide
Installation manual
Warranty information

Advertisement

loading

Summary of Contents for ABB Stanilite Nexus LX

  • Page 1 Nexus system Congratulations If the unit still does not work after checking these possible causes, contact ABB service in Australia on 1800 222 435, Congratulations on choosing to use this ABB product covered by our unique through-life support system. This document Monday to Friday, 7.00am to 5.00pm (AEST) and ask for help.
  • Page 2 LED on the unit is flashing green. Once commissioned, the LED changes to a install the unit, but replace it carefully into the packing box and notify the ABB product support hotline in Australia on steady red and flashes red during a test after receiving a command from the Nexus system.

This manual is also suitable for:

Stanilite nexus rf