CHAPTER 5: SETPOINTS
5.6.1
Plant
Condition

] PLANT CONDITION

]
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
5.6

S5 Monitoring

PATH: S5 MONITORING
PLANT CONDITION
The plant condition settings are programmed as follows:
DRIVE GREASING INTERVAL: Enter the interval at which the motor bearings must be
lubricated. When the motor running time exceeds this setpoint, a motor greasing
interval alarm is generated. Use the
setpoint to clear the motor running hours. If this feature is not required. set this
TIMERS
setpoint to "OFF".
CONTACTOR INSPECTION: Enter the interval at which the contactor contacts must be
inspected for wear. When the
contactor inspection interval alarm is generated. Use the
STATISTICS
CLEAR COUNTERS
this feature is not required set this setpoint to "OFF".
MAX DRIVE STOPPED TIME: Enter the maximum interval that the motor can be left not
running. When the motor stopped time exceeds this setpoint, a maximum motor
stopped time alarm is generated. Start the motor to clear the motor stopped time. If
this feature is not required set this setpoint to "OFF".
DRIVE GREASING
INTERVAL: OFF hrs
CONTACTOR INSPECTION
OFF x 1000 OPS
MAX DRIVE STOPPED
TIME: OFF hrs
S1 CONFIGURATION
NUMBER OF STARTS
setpoint to clear the NUMBER OF STARTS counter. If
S5 MONITORING
Range:
100 to 50000 hours or OFF in
steps of 100
Range:
1000 to 10000000 operations
or OFF in steps of 1000
Range:
10 to 10000 hours or OFF in
steps of 10
STATISTICS
CLEAR
counter exceeds this setpoint, a
S1 CONFIGURATION
5–35