MODBUS MEMORY MAP

8.4.1

Description

8–16
8.4
Modbus Memory Map
The data stored in the MM3 Motor Manager 3 is grouped into two areas: setpoints and
actual values. Setpoints can be read and written by a master computer. Actual values can
be read only. All setpoints and actual values are stored as two-byte values. That is, each
register address is the address of a two byte value. Addresses are listed in hexadecimal.
Data values (setpoint ranges, increments, factory values) are in decimal.
Table 8–2: Modbus Memory Map (Sheet 1 of 28)
Modicon
Address
dec.
hex
Actual values (input registers) addresses - 0000 to 0FFF
Product identification (read only actual values)
30001
0
0000
GE Multilin product device
code
30002
1
0001
Hardware version code
30003
2
0002
Main software version
code
30004
3
0003
Modification file number
30005
4
0004
Boot software version code
30006
5
0005
Supervisor processor
version code
30007
6
0006
GE Multilin product options
30008
7
0007
Serial number (characters
1 and 2)
30009
8
0008
Serial number (characters
3 and 4)
30010
9
0009
Serial number (characters
5 and 6)
30011
10
000A
Serial number (characters
7 and 8)
30012
11
000B
Manufacture month/day
30013
12
000C
Manufacture year
30014
13
000D
...Reserved...
30015
14
000E
Display processor version
code
30016
15
000F
...Reserved...
30017
16
0010
Switch input status
30018
17
0011
LED status flags 1
30019
18
0012
LED status flags 2
30020
19
0013
Operation status flags
* – Maximum setpoint value and 65535 represent OFF; ** – 1/phase current scale factor × A; *** – 101
represents unlimited;
† – Minimum setpoint value represents OFF; ~ – 0.1 × A when high resolution mode is disabled;
0.01 × A when enabled
Description
Range
---
---
---
---
---
---
---
---
---
---
---
---
---
...
---
...
Status (read only actual values)
---
---
---
---
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
CHAPTER 8: COMMUNICATIONS
Step
Units
Format
Default
---
---
F1
---
---
F4
current
version
---
---
F1
current
version
---
---
F1
mod.
number
---
---
F1
current
version
---
---
F1
current
version
---
---
F111
see
order
code
---
ASCII
F10
---
ASCII
F10
---
ASCII
F10
---
ASCII
F10
---
---
F33
---
---
F34
...
...
...
---
---
F1
...
...
...
---
---
F100
---
---
F101
---
---
F102
---
---
F103
71
---
---
---
---
---
---
...
---
...
---
---
---
---