[5-2 Outdoor Unit Control ]
5-2-13

Emergency Operation Mode

1. Problems with the outdoor unit
Emergency operation mode is a temporary operation mode in which the outdoor unit that is not in trouble operates when one
of the outdoor units in the P144 through P240 models is in trouble or when one or two of the outdoor units in the P264 througt
P360 models are in trouble. (The P144 and P168 models are combination models only.)
This mode can be started by performing an error reset via the remote controller.
(1) Starting the emergency operation
1) When an error occurs, the error source and the error code will be displayed on the display on the remote controller.
2) The error is reset using the remote controller.
3) If an error code appears that permits an emergency operation in step 1) above, (See the table below.), the retry operation
starts.
4) If the same error is detected during the retry operation (step 3 above), an emergency operation can be started by resetting
the error via the remote controller.
Error codes that permit an emergency operation (Applicable to both OC and OS)
Trouble source
0403
4220,4225,4226
4230,4235
Compressor
4240,4245
Fan motor
Inverter
4250,4255,4256
5110
5301
5305,5306
Thermistor
TH2
5102
TH3
5103
TH4
5104
TH5
5105
TH6
5106
TH7
5107
Power
4102
4115
Emergency operation pattern (2 outdoor units)
Emergency operation pattern (3 outdoor units)
OC
OS1
OS2
Cooling
Emergency
operation
Heating
Maximum total capacity
of indoor units (Note 1)
(Note 1) If an attempt is made to put into operation a group of indoor units whose total capacity exceeds the maximum allowable capacity,
some of the indoor units will go into the same condition as Thermo-OFF.
HWE14080
Error codes that permit an
emergency operation
Serial communication error
Bus voltage drop
Heatsink overheat protection
Overload protection
Overcurrent relay trip
Heatsink temperature sensor failure (THHS)
Current sensor/circuit failure
Position error
Subcool heat exchanger bypass outlet temperature sensor failure
Pipe temperature sensor failure
Discharge temperature sensor failure
Accumulator inlet temperature sensor failure
Subcool heat exchanger liquid outlet sensor failure
Outside air temperature sensor failure
Open phase
Power supply sync signal abnormality
OC
OS
Cooling
Emergency
operation
Heating
Maximum total capacity
of indoor units (Note 1)
OC failure
OS1 failure
pattern
pattern
Trouble
Normal
Normal
Trouble
Normal
Normal
Permitted
Permitted
Permitted
Permitted
60%
- 103 -
Error code description
OC failure
OS failure
pattern
pattern
Trouble
Normal
Normal
Trouble
Permitted Permitted
Permitted Permitted
60%
OS2 failure
OC, OS1 failure
OC, OS2 failure
pattern
pattern
pattern
Normal
Trouble
Normal
Trouble
Trouble
Normal
Permitted
Permitted
Permitted
Permitted
Permitted
Permitted
OS1, OS2 failure
pattern
Trouble
Normal
Normal
Trouble
Trouble
Trouble
Permitted
Permitted
40%
GB