[5-3 Operation Flowcharts ]

5-3

Operation Flowcharts

5-3-1

Operation Sequence Flowchart

(1) Indoor unit (cooling, heating, dry, fan mode)
Start
Breaker
turned on
Operation SW
turned on
1. Protection function
self-holding cancelled.
2. Indoor unit LEV fully closed.
Remote controller
display lit off
YES
Auxiliary heater
ON
1. Auxiliary heater OFF
FAN stop
2. Low fan speed for
1 minute
YES
Drain pump
ON
3-minute
drain pump ON
*Note 1. Indoor unit LEV fully closed : Opening 41.
*Note 2. The system may go into the error mode on either the indoor unit or the outdoor unit side. If some of the indoor units are
experiencing a problem (except water leakage), only those indoor units that are experiencing the problems will stop.
If the outdoor unit is experiencing a problem, all connected indoor units will stop.
*Note 3. The operation will be prohibited when the set cooling/heating mode is different from that of the outdoor unit.
HWE14080
NO
YES
1
From outdoor unit
YES
NO
*Note 1
*Note 2
NO
Error mode
YES
Error stop
NO
Error display
Cooling mode
Self-holding of
Cooling display
protection function
Error command
to outdoor unit
Prohibition
Indoor unit LEV
NO
fully closed.
*Note 1
Refer to 5-3-2 (1)
Cooling operation.
Normal operation
Error
Unit in the stopped state
Operation mode
Heating mode
Dry mode
Heating display
Dry display
*Note 3
*Note 3
YES
YES
Prohibition
Prohibition
NO
NO
Refer to 5-3-2 (2)
Refer to 5-3-2 (3)
Heating operation.
for dry operation.
Prohibition
"Blinking display on
the remote controller"
Operation command to outdoor unit (to 2 )
- 107 -
Fan mode
Fan display
*Note 3
YES
NO
Fan operations
GB