ABB REC670 Product Manual page 64

Relion 670 series, pre-configured
Hide thumbs Also See for REC670:

Advertisement

Bay control REC670
Pre-configured
Product version: 1.1
Monitoring
Table 58. Measurements CVMMXN
Function
Frequency
Voltage
Connected current
Active power, P
Reactive power, Q
Apparent power, S
Power factor, cos (φ)
Table 59. Supervision of mA input signals (MVGGIO)
Function
mA measuring function
Max current of
transducer to input
Min current of
transducer to input
Alarm level for input
Warning level for input
Alarm hysteresis for
input
Table 60. Event counter CNTGGIO
Function
Counter value
Max. count up speed
64
Range or value
(0.95-1.05) × f
r
(0.1-1.5) ×U
r
(0.2-4.0) × I
r
0.1 x U
< U < 1.5 x U
r
0.2 x I
< I < 4.0 x I
r
r
0.1 x U
< U < 1.5 x U
r
0.2 x I
< I < 4.0 x I
r
r
0.1 x U
< U < 1.5 x U
r
0.2 x I
< I < 4.0 x I
r
r
0.1 x U
< U < 1.5 x U
r
0.2 x I
< I < 4.0 x I
r
r
Range or value
± 5, ± 10, ± 20 mA
0-5, 0-10, 0-20, 4-20 mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(0.0-20.0) mA
Range or value
0-10000
10 pulses/s
1MRK 511 192-BEN B
Accuracy
± 2.0 mHz
± 0.5% of U
at U£U
r
± 0.5% of U at U > U
± 0.5% of I
at I £ I
r
± 0.5% of I at I > I
± 1.0% of S
at S ≤ S
r
r
± 1.0% of S at S > S
± 1.0% of S
at S ≤ S
r
r
± 1.0% of S at S > S
± 1.0% of S
at S ≤ S
r
r
± 1.0% of S at S > S
± 0.02
r
Accuracy
± 0.1 % of set value ± 0.005 mA
Accuracy
-
-
Issued: June 2010
r
r
r
r
r
r
r
r
r
r