Mitsubishi Electric 800 Series Instruction Manual page 24

Compact, high functionality inverters
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

NOTE
• The matrix shows the magnetic contactor selected according to the standards of Japan Electrical Manufacturers' Association
(JEM standards) for AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the MC is used for
emergency stops during motor driving, the electrical durability is 25 times. If using the MC for emergency stop during motor
driving, select the MC for the inverter input current according to the rated current against JEM 1038 standards for AC-3 class.
When installing an MC on the inverter output side to switch to the commercial-power supply operation while running a general-
purpose motor, select the MC for the rated motor current according to the rated current against JEM 1038 standards for AC-
3 class.
• When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the
inverter model, and select cables and reactors according to the motor output.
• When the breaker installed on the inverter input side is shut off, check for the wiring fault (short circuit), damage to internal
parts of the inverter etc. The cause of the output shutoff must be identified and removed before turning ON the power of the
breaker.
1
2
3
4
5
6
7
8
9
10
23
2. Installation and Wiring
2.1 Peripheral devices