Setting G.SOAK (Guarantee soak) items

Display
NOTE
(1) In the set value display state, move to the G.SOAK item to be set for the segment on
the programming map.
(2) Press the ENTER key to make display panel 1 flash (registration of first setting).
(3) Use the ↑, ↓, ←, and → keys to make the first setting – setting the G.SOAK type.
Setting range:
0: No G.SOAK
1: First G.SOAK segment
2: Last G.SOAK segment
3: Entire G.SOAK segment
(4) Press the ENTER key to stop the flashing on display panel 1 and display panel 2
starts flashing. (Start of second setting)
Note, however, that when the first setting is 0, "-----" is shown in the second panel
which does not flash.
(Pressing the FUNC and CLR keys causes display panel 1 and 2 to return to unset
g.S.0/
state "
-----" and the flashing stops.)
(5) Use the ↑, ↓, ←, and → keys to make the second setting (G.SOAK width).
Setting range: 0 to 1000 SPU
(6) Press the ENTER key to stop the flashing on display panel 2.
(Pressing the FUNC and CLR keys causes display panel 1 and 2 to return to unset
g.S.0/
state "
-----" and the flashing stops.)
Set G.SOAK type value
Set G.SOAK width value
G . S O A K T Y P E
B A N D
• Unset values are indicated as "
C59
• When setup data
is set to 1, a G.SOAK item on the programming map is skipped
and not displayed.
When a G.SOAK setting is something other than 0, it uses a subfunction.
A subfunction cannot be used when a setting has not been made "
0 to 3
PROG
Program
number
PROFILE
Pattern trend
g.S.0/
-----".
Chapter 8. PROGRAM SETUP
SEG
Segment
number
g.S.0/
-----".