External Switch Operation; External Switch Input - Honeywell DCP551 Mark ΙΙ User Manual

Digital control programmer
Table of Contents

Advertisement

Chapter 6. OPERATION

6-4 External Switch Operation

■ External switch input

●Types of external switch inputs
NOTE
6-8
A total of 16 external switch inputs are available. Each input is called SW1, SW2, etc.
up to SW16. (SW: external switch input)
SW1 to 4 and SW9 to 16 are tied.
SW5 to 8 functions are selected using setup data
SW9 to 16 are for program selections. Selections are made by entering BCD code or
binary codes in setup data
weight is for binary figures and the left is for BCD.
External
switch number
SW1
RUN
SW2
HOLD
SW3
RESET
SW4
ADV
SW5
Selects one of the following functions using setup settings.
SW6
RAMP-E
SW7
FAST
SW8
Clears G.SOAK using the OR condition.
Clears G.SOAK using the AND condition.
MANUAL/AUTO
AT start/stop
PV1/PV2 (OFF: PV1, ON: PV2)
AUTO Loading (the DCP551E***** model only)
PV1 → PV2 standby (See page 5-35.)
PV2 → PV1 standby (See page 5-35.)
Normal/Reverse operation
SW9
Selects program number, weight 1
SW10
Selects program number, weight 2
SW11
Selects program number, weight 4
SW12
Selects program number, weight 8
SW13
Selects program number, weight 10 or 16
SW14
Selects program number, weight 20 or 32
SW15
Selects program number, weight 40 or 64
SW16
Selects program number, weight 80 or 0
• When G.SOAK is cleared using an OR condition and an external switch is on, or PV
enters the G.SOAK width, a G.SOAK wait is cleared.
• When G.SOAK is cleared using an AND condition and an external switch is on and
PV enters the G.SOAK width, a G.SOAK wait is cleared.
• A normal or reverse operation is performed according to setup data setting
when the external switch is off. When the external switch is on, a normal or reverse
operation that is the reverse of setup data setting
C71
C75
. When two weights are given for an item, the right
Function
C23
C74
to
.
Detection way
Leading edge
Leading edge
Leading edge
Leading edge
Leading edge
Leading edge
Status
Status
Leading/trailing edge
Leading/trailing edge
Status
Leading edge
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
is performed.
C23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: