Basic Manual of Hitachi NE-S1 series inverter
Thank you for purchasing the Hitachi NE-S1 series inverter.
Please read this document and QRG(Quick Reference Guide), and understand perfectly how to handle
properly and the safety cautions of the product before operation, for safety and proper usage.
Note that this Manual is intended for each product and should be delivered to the end user of the inverter.
Safety precautions
Be sure to read this Instruction Manual and appended documents thoroughly before installing, operating the inverter.
Maintenance and service items in this manual are only caution related items. Read QRG (Quick Reference Guide) carefully before starting the
maintenance and service. (QRG can be downloaded from our website.)
In the Instruction Manual, safety instructions are classified into two levels, namely WARNING and CAUTION.
WARNING
: Indicates that incorrect handling may cause hazardous situations, which may result in serious personal injury or death.
: Indicates that incorrect handling may cause hazardous situations, which may result in moderate or slight personal injury or
CAUTION
physical damage alone.
CAUTION
Note that even a
instruction, which contains important safety information. Also focus on and observe the items and instructions described under "Notes" in the text.
Many of the drawings in the Instruction Manual show the inverter with covers and/or parts blocking your view being removed.
Do not operate the inverter in the status shown in those drawings. If you have removed the covers and/or parts, be sure to reinstall them in their
original positions before starting operation, and follow all instructions in the Instruction Manual when operating the inverter.
1. Installation
- Install the inverter on a non-flammable surface, e.g., metal. Otherwise, you run the risk of fire.
- Do not place flammable materials near the installed inverter. Otherwise, you run the risk of fire.
- When carrying the inverter, do not hold its top cover. Otherwise, you run the risk of injury and damage by dropping the inverter.
- Prevent foreign matter (e.g., cut pieces of wire, sputtering welding materials, iron chips, wire, and dust) from entering the inverter. Otherwise, you
run the risk of fire.
- Install the inverter on a structure able to bear the weight specified in the Instruction Manual. Otherwise, you run the risk of injury due to the inverter
falling.
- Install the inverter on a vertical wall that is free of vibrations. Otherwise, you run the risk of injury due to the inverter falling.
- Do not install and operate the inverter if it is damaged or its parts are missing. Otherwise, you run the risk of injury.
- Install the inverter in a well-ventilated indoor site not exposed to direct sunlight. Avoid places where the inverter is exposed to high temperature,
high humidity, condensation, dust, explosive gases, corrosive gases, flammable gases, grinding fluid mist, or salt water. Otherwise, you run the risk
of fire.
- The inverter is precision equipment. Do not allow it to fall or be subject to high impacts, step on it, or place a heavy load on it. Doing so may cause
the inverter to fail.
2. Wiring
- Be sure to ground the inverter. Otherwise, you run the risk of electric shock or fire.
- Commit wiring work to a qualified electrician. Otherwise, you run the risk of electric shock or fire.
- Before wiring, make sure that the power supply is off. Otherwise, you run the risk of electric shock or fire.
- Perform wiring only after installing the inverter. Otherwise, you run the risk of electric shock or injury.
- The inverter must be powered OFF before you change any of the slide switch settings.Otherwise, you run the risk of electric shock or injury.
Make sure that the voltage of AC power supply matches the rated voltage of your inverter. Otherwise, you run the risk of injury or fire.
- Do not input single-phase power into the 3-phase inverter. Otherwise, you run the risk of fire.
- Do not connect AC power supply to any of the output terminals (U, V, and W). Otherwise, you run the risk of injury or fire.
- NE-S1 series inverter do not have terminals for braking resistor. Do not connect the resistor. Otherwise there is a risk of fire.
- Connect an earth-leakage breaker to the power input circuit. Otherwise, you run the risk of fire.
- Use only the power cables, earth-leakage breaker, and magnetic contactors that have the specified capacity (ratings). Otherwise, you run the risk
of fire.
- Do not use the magnetic contactor installed on the primary and secondary sides of the inverter to stop its operation.
- Tighten each screw to the specified torque. No screws must be left loose. Otherwise, you run the risk of fire.
- Before operating slide switch in the inverter, be sure to turn off the power supply. Otherwise, you run the risk of electric shock and injury.
- Please make sure that earth or ground screw is tighten properly and completely.
- First, check the screws of output terminal (U, V and W) are properly tighten, and then tighten the screws of input terminal (R,S and T)
level situation may lead to a serious consequence according to circumstances. Be sure to follow every safety
CAUTION
CAUTION
WARNING
CAUTION
1
NT341BX

Advertisement

Table of Contents
loading

Summary of Contents for Hitachi NES1-OP

  • Page 1 Basic Manual of Hitachi NE-S1 series inverter Thank you for purchasing the Hitachi NE-S1 series inverter. Please read this document and QRG(Quick Reference Guide), and understand perfectly how to handle properly and the safety cautions of the product before operation, for safety and proper usage.
  • Page 2 3. Operation WARNING - While power is supplied to the inverter, do not touch any terminal or internal part of the inverter, check signals, or connect or disconnect any wire or connector. Otherwise, you run the risk of electric shock or fire. - Be sure to close the top cover before turning on the inverter power.
  • Page 3 Cautions for UL and cUL (Standard to comply with : UL508C,CSA C22.2 No.14-05) Wiring diagram of inverter DC link choke Circuit breaker or Fuse Power Motor supply Inverter Maximum surrounding air temperature rating of 50ºC. Solid State motor overload protection reacts with max. 150 % of FLA. Suitable for use on a circuit capable of delivering not more than 100,000 rms Symmetrical Amperes, 240 Volts Maximum.
  • Page 4 The warranty period under normal installation and handling conditions shall be two (2) years from the date of manufacture, or one (1) year from the date of installation, whichever occurs first. The warranty shall cover the repair or replacement, at Hitachi's sole discretion, of ONLY the inverter that was installed.
  • Page 5: Cautions For Installation

    P8 to 9 P8 to 9 ⑩ Charge indicator lamp Name Description Connector for dedicated operator Dedicated operator for NE-S1 (NES1-OP) can be connected on this connector. ① for NES1-OP RUN/STOP/RESET key Push key for run, stop and reset operation. ②...
  • Page 6 ②Ensure Adequate Ventilation To summarize the caution messages – you will need to find a solid, non-flammable, vertical surface that is in a relatively clean and dry environment. In order to ensure enough room for air circulation around the inverter to aid in cooling, it is recommended to maintain the specified clearance and the inverter specified in the below diagram.
  • Page 7 ⑦Cautions for installation into the cabinet Please pay attention to the location of the ventilation holes of the inverter and the cabinet, in case of side-by-side installation and using ventilation fan. cooling performance of the inverter highly depends on the location of the holes. Please pay high attention to the ambient temperature of the Ventilation inverter to be less than the specified value.
  • Page 8: Wiring And Terminal Description

    4.2 Wiring and terminal description Power source, U/T1 (L1) R/L1 3-phase or S/L2 1-phase, per V/T2 (N N N N ) inverter model T/L3 W/T3 Short circuit bar DC24V Motor Refer to QRG (section 5.7) when using Short circuit bar external equipment for source logic PD/+1 output and/or external power supply.
  • Page 9 (2) Control terminal description Category Symbol Name Description Electrical characteristics Common for internal control power supply, digital Common for input signals Power inputs/outputs, analog inputs/outputs supply Power supply for external DC10V power supply. Used with variable resistor for O Max.10mA withdraw potentiometer input.
  • Page 10: Mains Wiring

    A special filter to suppress the surge voltage is available. If you need this filter, contact your supplier or local Hitachi Distributor. ・ When connecting multiple motors to the inverter, connect a thermal relay to the inverter output circuit for each motor.
  • Page 11 EX30 (20A) Note 1)The peripheral equipment described here is applicable when the inverter connects a standard Hitachi 3-phase, 4-pole squirrel-cage motor. Note 2)Select breakers that have proper capacity. (Use breakers that comply with inverters.) Select above proper ELB capacity following above table for the 1pc inverter.
  • Page 12: Confirmation Before Power Up The Inverter

    - Standard panel : Confirm that both PWR lamp and Key valid lamp are emitting - Dedicated operator (NES1-OP) : Confirm that the PWR lamp is emitting. Display will be the one set by b038 (Initial display selection). “0.00(output frequency monitor)” will be displayed under default condition.
  • Page 13: Names And Functions Of Components

    Power ON. In case of Modbus communication, it is necessary to set the changeover ⑥RS422/RS485 port (RJ45) switch and parameter (C070). Display of NES1-OP will be according to the parameter set of b150 continuously, if the external operator is connected while the dedicated operator (NES1-OP) is integrated. Note2) Note 1) It is necessary to set changeover switch and the parameter C070 for releasing the Modbus communication.
  • Page 14 ※ One of the following is required when changing parameters on NE-S1 series inverters. 20Hz order ① Dedicated operator (NES1-OP) ② Digital operator ③ 5-line LCD operator ④ Modbus ⑤ PC programming tool (ProDriveNext) (2) Method to perform driving in RUN/STOP/RESET key and perform frequency setting in speed potentiometer This is the operation method using Run command is given by "RUN/STOP/RESET key"...
  • Page 15: Specifications

    Standards Compliance UL、CE、c-UL、c-tick Note1) The applicable motor refers to Hitachi standard 3-phase motor (4p). When using other motors, care must be taken to prevent the rated motor current (50/60Hz) from exceeding the rated output current of the inverter. Note2) The output voltage decreases as the main supply voltage decreases (except when using the AVR function). In any case, the output voltage cannot exceed the input power supply voltage.
  • Page 16 NES1-007LB NES1-015LB NES1-022LB SUITABILITY FOR USE Hitachi Industrial Equipment Systems shall not be responsible for conformity with any standard, codes, or regulations that apply to the combination of products in the customer’s application or use of the products. Take all necessary steps to determine the suitability of the product for the Systems, machines, and equipment with which it will be used.