NOTE
• The selection example is for the ND rating. For selecting the SLD rating, LD rating, or HD rating, refer to the Instruction Manual (Detailed).
• Tighten the terminal screw to the specified torque. A screw that has been tightened too loosely can cause a short circuit or malfunction. A screw that has been
tightened too tightly can cause a short circuit or malfunction due to the unit breakage.
• Use crimp terminals with insulation sleeves to wire the power supply and motor.
2.3
Control circuit terminal
 Wiring precautions
• It is recommended to use a cable of 0.3 to 0.75 mm
• The wiring length should be 30 m (200 m for the terminal FM) at the maximum.
• Use two or more parallel micro-signal contacts or twin contacts to prevent contact faults when using contact inputs since
the control circuit input signals are micro-currents.
• To suppress EMI, use shielded or twisted cables for the control circuit terminals and run them away from the main and
power circuits (including the 200 V relay sequence circuit). For the cables connected to the control circuit terminals,
connect their shields to the common terminal of the connected control circuit terminal. When connecting an external
power supply to the terminal PC, however, connect the shield of the power supply cable to the negative side of the external power supply. Do not directly earth
(ground) the shield to the enclosure, etc.
• Always apply a voltage to the fault output terminals (A1, B1, C1, A2, B2, C2) via a relay coil, lamp, etc.
• Do not connect any terminal SD on the inverter and the 0V terminal of the external power supply (when the sink logic is selected).
 Wiring method
• Crimp terminals commercially available (as of April 2019)
2
Wire gauge (mm
)
With insulation
sleeve
0.3
AI 0,34-10TQ
0.5
AI 0,5-10WH
0.75
AI 0,75-10GY
1
AI 1-10RD
1.25, 1.5
AI 1,5-10BK
0.75 (for two wires)
AI-TWIN 2×0,75-10GY

A ferrule terminal with an insulation sleeve compatible with the MTW wire which has a thick wire insulation.

Applicable for the terminal A1, B1, C1, A2, B2 and C2 only.
2
Blade terminal part No.
Wire gauge (mm
)
0.3 to 0.75
BT 0.75-11
2.4
CC-Link IE TSN function
 CC-Link IE TSN communication specifications
The communication specification varies depending on the specification of the master.
Item
Transmission speed
Minimum synchronization cycle
CC-Link IE TSN conformance class
Communication method
Synchronization function
Maximum number of connected units
Maximum distance between nodes
Maximum number of branches
Topology
Connection cable
Connector
Node type
RX
RY
Maximum cyclic size (of one node)
RWr
RWw
2
for connection to the control circuit terminals.
Ferrule part No.
Without insulation
For UL wire
sleeve
AI 0,5-10WH-GB
A 0,75-10
AI 0,75-10GY-GB
A 1-10
AI 1-10RD/1000GB
A 1,5-10
AI 1,5-10BK/1000GB
Insulation cap part
No.
VC 0.75
1 Gbps/100 Mbps
125.00 μs
B
Time sharing method
Compliant with IEEE 802.1AS and IEEE 1588v2
121 units (sum of master and slave stations)
100 m
No upper limit within the same Ethernet system
Line, star, ring, or a combination of line and star
Ethernet cable
(IEEE 802.3 1000BASE-T compliant cable or ANSI/TIA/EIA-568-B (Category 5e) compliant shielded 4-pair branched
cable)
Shielded RJ-45
Slave station
64 bits
64 bits
128 words
128 words
Manufacturer

Phoenix Contact Co., Ltd.

Crimping tool
Manufacturer
model No.
NICHIFU Co., Ltd.
NH 69
Description
Control circuit terminal
Micro signal contacts
Twin contacts
Crimping tool
model No.
CRIMPFOX 6
7
WIRING