Trouble
Trouble Annunciation
Siemens Building Technologies
Fire Safety
The SUPERVISORY LED glows steadily to indicate that all supervisories are acknowl-
edged. If there are no troubles or security conditions in the System, the internal
audible goes silent; if any of those conditions still exist, the internal audible pulses.
When a trouble is detected, the System causes the TROUBLE LED on the MKB to
flash, the System's internal audible to sound, and the display on the MKB to display
the event in the following format:
40 Characters
1
TBL CUSTOM MESSAGE
2
TBL CUSTOM MESSAGE
3
4
5
6
7
8
9
TBL CUSTOM MESSAGE
10
ALR=000, SUP=000, TBL=002, SEC=000
11
SIEMENS BUILDING TECHNOLOGIES
12
13
1-001
FP-11
14
002
ASD Testing Enabled
15
11:59:59 Dec 31, 02
Example shown is Canadian Display
Figure 7
TROUBLE Event Screen With More Info Key Pressed
In addition, the System responds to troubles with programmed output functions.
In Figure 7 , 1-001 represents the address of the device reporting the trouble. 002 on
Line 14 in the More Info area (Lines 13-15) tells you that this is the second (and the
most recent) of two troubles received.
The status information shown in Line 10 reports the total of alarms, supervisories,
troubles, and security conditions.