UPS5000-E-(50 kVA–300 kVA) User Manual (50 kVA Power Modules) Issue Date 2022-01-30 HUAWEI TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
About This Document About This Document Purpose This document describes the UPS5000-E-(50 kVA–300 kVA) in terms of its features, performance, working principles, appearance as well as instructions for installation, and operation and maintenance (O&M). UPS is short for uninterruptible power system.
Configuration ● SM: standard configuration type ● FM: full configuration Cable routing Routed from the top (only the UPS5000-E-300K-SMT model contains "T") This document describes the following UPS models: ● UPS5000-E-200K-SM/FM The models provide four configurations: 50 kVA, 100 kVA, 150 kVA, and 200 kVA.
NO TE ● The UPS5000-E-200K-SM supports cable routing from the top or bottom. ● The UPS5000-E-200K-FM supports cable routing from the top and can support cable routing from the bottom if a cable entry cabinet is installed for the non-isolation protection model.
UPS5000-E-(50 kVA–300 kVA) User Manual (50 kVA Power Modules) 2 Overview 2.3.1 Structure Figure 2-8 UPS5000-E-200K-SM front view (1) Power modules (2) Bypass module (3) Control module (4) Power distribution subrack cover (5) Filler panels (6) Monitor display (7) Maintenance...
Page 33
UPS5000-E-(50 kVA–300 kVA) User Manual (50 kVA Power Modules) 2 Overview Figure 2-9 UPS5000-E-200K-FM front view (1) Power distribution (2) Bypass input switch (3) Maintenance (4) Mains input switch subrack cover bypass switch (5) Output switch (6) Control module (7) Bypass module...
Page 34
UPS5000-E-(50 kVA–300 kVA) User Manual (50 kVA Power Modules) 2 Overview Figure 2-10 UPS5000-E-200K-FM (isolation protection) front view (1) Cover (2) Mains input switch (3) Bypass input switch (4) Maintenance bypass switch (5) Output switch (6) Control module (7) Bypass module...
Page 35
UPS5000-E-(50 kVA–300 kVA) User Manual (50 kVA Power Modules) 2 Overview Figure 2-11 UPS5000-E-300K-SM front view (1) Power modules (2) Bypass module (3) Control module (4) Power distribution subrack cover (5) Monitor display (6) Filler panels (7) Maintenance (8) Folder...
Page 36
UPS5000-E-(50 kVA–300 kVA) User Manual (50 kVA Power Modules) 2 Overview Figure 2-12 UPS5000-E-300K-SMT front view (1) Power distribution (2) Maintenance (3) Control module (4) Bypass module subrack cover bypass switch (5) Power modules (6) Monitor display (7) Filler panels...
Page 37
UPS5000-E-(50 kVA–300 kVA) User Manual (50 kVA Power Modules) 2 Overview Figure 2-13 UPS5000-E-300K-SMT (isolation protection) front view (1) Cover (2) Maintenance (3) Control module (4) Bypass module bypass switch (5) Power modules (6) Monitor display unit Issue 15 (2022-01-30)
Page 60
● The IP21 component cannot be configured for the UPS5000-E-300K-SMT and UPS5000- E-200K-FM. If cables are routed in and out from the top for the UPS5000-E-200K-SM, the IP21 component cannot be configured. ● A cable entry cabinet can be installed only for the non-isolation protection model of UPS5000-E-200K-FM.
Page 68
DC power cable should not be longer than 50 meters. Table 3-3 Table 3-4 list the requirements for power cable terminals of the UPS5000-E-200K-SM/FM. Table 3-3 Power cable terminal requirements for the UPS5000-E-200K-SM Port Connection Bolt Bolt Hole...
Page 83
UPS5000-E-(50 kVA–300 kVA) User Manual (50 kVA Power Modules) 3 Installation Figure 3-21 Position of a battery grounding failure detector in a UPS5000-E-200K- (1) Battery grounding failure detector Figure 3-22 Position of a battery grounding failure detector in a UPS5000-E-200K-...
Page 84
UPS5000-E-(50 kVA–300 kVA) User Manual (50 kVA Power Modules) 3 Installation Figure 3-23 Position of a battery grounding failure detector in a UPS5000-E-200K- FM (isolation protection) (1) Battery grounding failure detector Figure 3-24 Position of a battery grounding failure detector in a UPS5000-E-300K-...
Page 85
UPS5000-E-(50 kVA–300 kVA) User Manual (50 kVA Power Modules) 3 Installation Figure 3-25 Position of a battery grounding failure detector in a UPS5000-E-300K- (1) Battery grounding failure detector Figure 3-26 Position of a battery grounding failure detector in a UPS5000-E-300K-...
UPS5000-E-(50 kVA–300 kVA) User Manual (50 kVA Power Modules) 3 Installation 3.2.10 Routing Cables (UPS5000-E-300K-SMT, Isolation Protection) Context NO TICE ● Route cables for the UPS from inside out and from bottom up. Procedure Step 1 Ensure the maintenance bypass switch is OFF. Open the front door, remove the front cover, and remove covers from the top of the cabinet based on the site requirements.
UPSs and then use screws to tighten the connecting kits to the cabinet according to the following figures: ● Figure 3-110 shows the connection point for the UPS5000-E-200K-SM and UPS5000-E-300K-SM/SMT. ● Figure 3-111 shows the connection point for the UPS5000-E-200K-FM.
----End 3.3.2 Connecting Power Cables Context Cable connection for the UPS5000-E-200K-SM is used as an example. The parallel power cables for different UPS models can be connected in a similar way. Procedure Step 1 Ground each UPS in a parallel system separately, and connect power cables and battery cables according to 3.2 Installing a Single...
Page 154
2. After verifying the installation, reinstall all the covers. 3. Do not remove the dustproof cover before power-on to prevent dust inside the UPS. Figure 3-119 Positions for checking foreign matter (UPS5000-E-200K-FM) (1) Cabinet top (2) Wiring terminal...
Page 157
UPS5000-E-(50 kVA–300 kVA) User Manual (50 kVA Power Modules) 3 Installation Figure 3-122 Positions for checking foreign matter (UPS5000-E-300K-SMT, isolation protection) (1) Rear of modules (2) Cabinet top (3) Wiring terminal (4) Switches blocks Figure 3-123 Fill the holes with sealing putty...
UPS5000-E-(50 kVA–300 kVA) User Manual (50 kVA Power Modules) 4 Operations Figure 4-21 Turning on the maintenance bypass switch (UPS5000-E-300K-SMT, isolation protection) NO TE After the system transfers to maintenance bypass mode, the Maint. breaker closed and Bypass mode alarms are displayed on the LCD.
Page 203
UPS5000-E-(50 kVA–300 kVA) User Manual (50 kVA Power Modules) A (Optional) TN-C System Application Figure A-6 Connecting the input N and PE (UPS5000-E-300K-SMT, isolation protection) Table A-1 Recommended cross-sectional areas for cables Model Current (A) Recommended Cross- Sectional Area (mm UPS5000-E-200K-SM/FM 335.4...