TYPE
MITSUBISHI Pressure Ventilator (for device cooling)
MODEL
Power supply
Three-phase 200-220 V
Blade type
35 cm metal propeller vane
Motor type
Totally enclosed 3-phase induction motor
(4-pole type A)
Temperature: –15℃ to +50℃
Ambient operating
Relative humidity: 90% or less (normal
conditions
temperature)
Indoor use
Load side: 6003DDW NC
Ball bearings
Reverse load side: 6003ZZ NC
Grease: Urea
Frequency
(Hz)
SPECIFICATIONS
60
IEC/EN 60335-1
IEC/EN 60335-2-80
IEC/EN 61000-6-1
Conforming
standard number
IEC/EN 61000-6-2
(IEC/EN)
IEC/EN 61000-6-3
IEC/EN 61000-6-4
UL 507
Conforming
standard number
UL 1004-1
(UL)
UL 1004-3
UL File No.
E474618
※ Air volume and power consumption are measured based on JIS C 9603.
The noise, power consumption and current are measured under free air condition.
※ The value of the noise is at 1.5 m from the front and both sides of the appliance
in an anechoic room. (Average of the three points)
■Attention
※ Refer to the precautions on page 2.
■Drawings and Dimensions
■Connection Diagram
Dim. in
Third Angle
Projection Method
mm
MITSUBISHI ELECTRIC NAKATSUGAWA WORKS
EF-35UDT-GL
Air volume
Noise
3
(dB)
(m
/h)
3600
49-49.5
Household and similar electrical appliances-Safety-Part1 : General requirements
Household and similar electrical appliances-Safety-Part2-80 : Particular requirements for fans
Electromagnetic compatibility (EMC)-Part6-1 : Generic standards-Immunity for residential, commercial and
Electromagnetic compatibility (EMC)-Part6-2 : Generic standards-Immunity for industrial environments
Electromagnetic compatibility (EMC)-Part6-3 : Generic standards-Emission standard for residential, commercial
Electromagnetic compatibility (EMC)-Part6-4 : Generic standards-Emission standard for industrial environments
Standard for Electric Fans
Standard for Rotating Electric Machines - General Requirements
Standard for Thermally Protected Motors
Scale
Date
Non proportional
Sep 2017
Withstand voltage
Insulation resistance
Weight
Color
Material
Power
Current
consumption
(A)
(W)
180-185
0.8-0.85
light-industrial environments
and light-industrial environments
※This appliance is only for exhaust-use.
※The nominal output is only a rough estimate. When
selecting a breaker or an overload protection device,
select it according to the maximum load current
value. (Refer to page 2 for details.)
■Characteristics
200V
220V
※ The air volume was measured using the orifice
chamber method.
MITSUBISHI Pressure Ventilator (for device cooling)
Model
Number
NJ215016B-60 (1/2)
VOLUME
SIGN
2000 V AC 1 minute
10 MΩ or more
(with 500 V Insulation resistance tester)
9.2 kg
Munsell: 7.65Y7.6/0.7
Body frame, Vane, Motor leg, Motor cover:
Polyester coating
Vane: Steel sheet
Motor leg: Flat bar
Body frame, Motor, Motor cover:
Galvanized sheet steel
Maximum
Starting
load current
current
(A)
(A)
1.15-1.14
4.96-5.28
EF-35UDT-GL
Specification
Nominal
output
(W)
150

Advertisement

loading

Summary of Contents for Mitsubishi Electric EF-35UDT-GL

  • Page 1 ■Connection Diagram ※ The air volume was measured using the orifice chamber method. Dim. in Scale Date MITSUBISHI Pressure Ventilator (for device cooling) Third Angle Model Projection Method EF-35UDT-GL Non proportional Sep 2017 MITSUBISHI ELECTRIC NAKATSUGAWA WORKS Number NJ215016B-60 (1/2) Specification...
  • Page 2 This appliance is specialized for indirect export. Thus, it cannot be sold outside Japan and cannot be used in Japan. No servicing is available outside of Japan. Dim. in Scale Date MITSUBISHI Pressure Ventilator (for device cooling) Third Angle Model Projection Method Non proportional Sep 2017 EF-35UDT-GL MITSUBISHI ELECTRIC NAKATSUGAWA WORKS Number NJ215016B-60 (2/2) Specification...