Installation Preparations
1.
Before installing the devices, read the user manual carefully to get familiar with product information and safety precautions.
2.
Use insulated tools during installation.
3.
Only engineers certified by Huawei or its agents are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the UPS faults
caused are beyond the warranty scope of Huawei.
4.
When routing power cables and communications cables, prevent cables from being scratched by cabinet components.
Model
UPS2000-H-6KRTL-Li
UPS2000-H-10KRTL-Li
Number
Model
Wiring Terminal
Rated Voltage
of Phases
AC input
L/N/PE
1
220 V AC/230 V
AC/240 V AC
6 kVA (single-
AC output
L/N/PE
1
phase input
+
single-phase
-
output)
Battery
2
54 V DC
PE
AC input
L/N/PE
1
220 V AC/230 V
10 kVA (single-
AC/240 V AC
AC output
L/N/PE
1
phase input
single-phase
+
output)
Battery
-
2
54 V DC
PE
AC input
L/N/PE
3
380 V AC/400 V
10 kVA (three-
AC/415 V AC
phase input
AC output
L/N/PE
1
single-phase
+
output)
-
Battery
2
54 V DC
PE
+
Lithium battery
-
2
54 V DC
PE
02
Installing a UPS
Typical Rack-mounted Scenario
The following uses two 6 kVA UPSs and
two lithium batteries in rack-mounted
mode without a junction box as an
Installing Mounting Ears
example.
The installation of the 6 kVA UPS is similar to that of the
10 kVA UPS. This document uses the 6 kVA UPS as an
example. Perform operations based on the actual
situation.
A UPS supports a maximum of eight lithium batteries in
parallel.
It is recommended that the BBB box be installed behind
the lithium batteries.
If four groups of batteries are installed in the rack-
mounted mode, reserve 1 U space between each two
groups of lithium batteries for battery cables.
You are advised to reserve 1 U space between UPSs, 1 U
space between the UPS and lithium battery, and 1 U space
above the UPS.
UPS2000-H-(6 kVA–10 kVA) Quick Guide
Weight
Dimensions (H x W x D)
14 kg
43 mm x 430 mm x 514 mm
17 kg
86 mm x 430 mm x 514 mm
External Circuit
Cable Cross-sectional
Terminal Type
Note
Breaker
Area
2
2
50 A (feature C)
10 mm
OT-10 mm
-M6 terminal
2
2
40 A (feature D)
6 mm
OT-6 mm
-M6 terminal
2
2 x 25 mm
a
2
160 A
OT-25 mm
-M6 terminal
2 x 25 mm
2
M4 screw tightening torque
OT-6 mm
2
-90°bending-M4
Torque for tightening screws: 4.8 N·m
-
2 x 6 mm
2
terminal
Notes:
80 A (feature C)
16 mm
2
OT-16 mm
2
-M6 terminal
2
2
63 A (feature D)
16 mm
OT-16 mm
-M6 terminal
2 x 35 mm
2
a
2
250 A
OT-35 mm
-M6 terminal
2
2 x 35 mm
-
2
2
2 x 6 mm
OT-6 mm
-M6 terminal
b
2
2
80 A
(feature C)
16 mm
OT-16 mm
-M6 terminal
2
2
63 A (feature D)
16 mm
OT-16 mm
-M6 terminal
2
2 x 35 mm
a
250 A
2
OT-35 mm
-M6 terminal
2
2 x 35 mm
-
2
2
2 x 6 mm
OT-6 mm
-M6 terminal
2
25 m
OT-25 mm
2
-M6 terminal
2
-
25 mm
2
2
6 mm
OT-6 mm
-M6 terminal
Installing Guide Rails
install four floating nuts.
Securing the UPS and Lithium batteries.
UPS Dimensions and Space Planning (6 kVA)
Rack-mounted
6 kVA UPS
(1 U)
Reserved space
:
(1 U)
1.2 N·m
Lithium battery
(3 U)
Use flexible conductors with a working
temperature of 90℃ or softer conductors
for power cables. Cables with solid
conductors or twisted conductors may fail
to be installed.
If there is no battery bus bar (BBB) box,
connect battery cables to the UPS. Select OT
Tower-mounted
terminals based on the battery cables.
a: The lithium battery is equipped with a
circuit breaker.
b: In bypass mode, the UPS obtains power
from phase A. The input current is the
6 kVA UPS
three-phase total current.
(1 U)
Lithium battery
(3 U)
Subrack
Connect the COM port on
the UPS to the COM_IN
port on the lithium battery.
If the build-out resistor is not installed,
the communication between the UPS
and batteries will fail.
1
Issue: 02
Date: 2021-10-13
UPS Dimensions and Space Planning (10 kVA)
Unit: mm
Rack-mounted
10 kVA UPS
(2 U)
Reserved space
(1 U)
Lithium battery
(3 U)
Tower-mounted
10 kVA UPS
(2 U)
Lithium battery
(3 U)
Subrack
Installing Optional Components
SNMP
Connect cables to the lower
UPS and then to the upper
UPS.
T/H sensor
4G Module
Unit: mm
Dry Contact Card
Ethernet
User equipment
The 4G module is
connected to the USB
port of the SNMP card
through a USB
extension cable. The
4G module is magnetic
and can be mounted
to the near cabinet.

Advertisement

loading

Summary of Contents for Huawei UPS2000-H-6 kVA

  • Page 1 Before installing the devices, read the user manual carefully to get familiar with product information and safety precautions. Use insulated tools during installation. Only engineers certified by Huawei or its agents are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the UPS faults Unit: mm Unit: mm caused are beyond the warranty scope of Huawei.
  • Page 2 OFF to prevent operations with power on. If the input or output cables has to be changed, contact Huawei technical support if you are not familiar with the operation. Do not power on the UPS directly.
  • Page 3 UPS2000-H-(6 kVA–10 kVA) Quick Guide Installing AC Power Cables (Parallel System) Install the cabinet. 6 kVA Single-Phase Input Single-Phase Output 10 kVA Single-Phase Input Single-Phase Output 10 kVA Three-Phase Input Single-Phase Output Ensure that the AC input and output power cables on each UPS are connected in the same phase sequence, battery terminals are connected correctly, and the bypass power cables...
  • Page 4 Switch off the mains AC input circuit breaker K1 and output circuit breaker Q1 of the UPS. After all indicators turn off and fans stop, the UPS shuts down, and the loads power off. You can also log in to https://support.huawei.com/enterprise Huawei technical support https://support.huawei.com website: Copyright © Huawei Technologies Co., Ltd. 2021. All rights reserved.