R100020G1 Charging Module
User Manual
Setting the Output Voltage
Table 2-6 Procedure description
Procedure
1
2
3
4
5
6
7
8
Issue 05 (2021-11-16)
Hold down the left or right button (for at least 3s) to enter the parameter
setting state or save the current settings.
NO TE
Hold down the left or right button to enter the parameter setting state. If no operation is
performed within 60s, the setting state is automatically exited and the parameter settings
are not saved.
The output voltage can be set only after the mode is switched from Auo to
dEG.
The voltage settings of the charging module are not saved upon power
failure.
If the mode is switched from dEG to Auo, the charging module outputs
according to the system monitoring command.
Operation
Press the left or right button
to switch to the mode display
state.
Hold down the left or right
button to enter the setting
state.
Press the right button to
switch to the dEG mode.
Hold down the left or right
button to enter the display
state.
Press the left or right button
to switch to the output
voltage display state.
Hold down the left or right
button to enter the setting
state.
Press the left button to switch
between the high-, middle-,
and low-order nixie tubes.
Press the right button to
adjust the value.
Hold down the left or right
button to save the settings.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Nixie Tube Display
Auo (static)
Auo (blinking)
dEG (blinking)
dEG (static)
Current output voltage (static)
Current output voltage (high-,
middle-, or low-order nixie tube
blinking)
Adjusted output voltage (high-,
middle-, or low-order nixie tube
blinking)
Actual output voltage (static)