Commissioning
1. Turn on the air supply to the positioner.
2. Apply the 4...20 mA analog input signal to the positioner.
3. Check for proper mounting:
-
Press and hold
-
Additionally briefly press
range) is displayed.
-
Release
MODE
-
Press
or
note the values. The angle of rotation is indicated in degrees.
Recommended positions of limit stops:
> -28° and < +28° for linear actuators
> -57° and < +57° for rotary actuators
Minimum angle: 25°
4. Switch to the configuration level:
-
Press and hold
-
Additionally briefly press
-
Wait until the countdown from 3 to 0 is completed.
-
Release
and
The device will automatically go to parameter group P1.
5. Select the actuator type (parameter P1); select ROTARY or LINEAR using
This step must be performed prior to Autoadjust (step 6).
Caution
6. Start Autoadjust:
-
Press and hold
-
Additionally briefly press
-
Release
MODE
-
Press
ENTER
-
Release
ENTER
Autoadjust is started.
-
If the message "COMPLETE" is displayed to indicate successful Autoadjust, briefly
press
ENTER
It is also possible that Autoadjust is automatically cancelled due to troubles, and an
error message is displayed. See "P 1.1 Autoadjust" on page 53 for details.
42/18-64-4 EN
.
MODE
or
until mode 1.3 (manual adjustment within the sensor
.
to move the actuator to its mechanical limit stops in both directions, and
and
simultaneously.
.
ENTER
.
.
MODE
; until "P1.1" is indicated.
.
and keep it pressed until the countdown is finished.
.
to acknowledge.
Brief operating instructions
Brief operating instructions
or
.