Brief operating instructions
Read and observe the safety instructions in chapter 1 of these operating
instructions.
Caution

Mechanical mounting

see fold-out drawing

Pneumatic connection

Connect the air supply to the in port. Air supply range must be between 1.4 and 6 bar
(20 to 90 psi).
Caution: Do not exceed the max. pressure of the actuator!
Connect the actuator supply to the OUT1 port (and OUT2 port for double acting actuators).

Electrical connection

Make the electrical connections according to the following terminal designation:
+11/-12
Analog input, 4...20 mA signal
+31/-32
Analog output, position feedback, 4...20 mA signal*
+41/-42
Digital position feedback, SW1 *
+51/-52
Digital position feedback, SW2 *
+81/-82
Digital input
+83/-84
Digital output, alarm contact
+41/-42
Kit for digital position feedback, Limit 2*
+51/-52
Kit for digital position feedback, Limit 1*
+41/-42
Shutdown module*
41
Kit for digital position feedback, 24 V microswitch, Limit 1, NC contact *
42
Kit for digital position feedback, 24 V microswitch, Limit 1, NO contact*
43
Kit for digital position feedback, 24 V microswitch, Limit 1, input*
51
Kit for digital position feedback, 24 V microswitch, Limit 2, NC contact*
52
Kit for digital position feedback, 24 V microswitch, Limit 2, NO contact*
53
Kit for digital position feedback, 24 V microswitch, Limit 2, input*
* Option
a
Brief operating instructions
Brief operating instructions
42/18-64-4 EN