Maintenance / Repair; Function Check; Testing Detector With The Key - Siemens FDM1101-Rx Technical Manual

Manual call point collective
Table of Contents

Advertisement

Maintenance / Repair

7
Maintenance / Repair
7.1

Function check

7.2

Testing detector with the key

24
Building Technologies
Fire Safety & Security Products
The devices are automatically subjected to a performance check during the self-
test. Nevertheless, it is necessary to check the devices on site at regular intervals.
Recommendation:
Check the devices every year.
Replace heavily soiled or damaged devices.
No other special maintenance work is necessary.
NOTICE
False alarm
Switch the manual call point to 'Test' on the control panel.
Procedure
1
Testing
1. Insert the key into the manual call point until the switching unit moves.
The manual call point has been triggered.
2. To arm the manual call point, pull out the key again.
The switching unit is in a straight position and the detector is armed.
WARNING
Deactivating the manual call points prevents alarms from being forwarded.
The alarm does not take place.
Deactivated manual call points must be labeled with the 'NOT IN USE' label!
2
A6V10201150_a_en_--
05.06.2008