Mitsubishi Electric CMB-WM350F-AA Installation Manual

Air-conditioners for building application, indoor unit
Hide thumbs Also See for CMB-WM350F-AA:

Advertisement

Quick Links

Air-Conditioners For Building Application
INDOOR UNIT
CMB-WM350F-AA, CMB-WM500F-AA
CMB-WM108V-BB, CMB-WM1016V-BB
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
INSTALLATIONSHANDBUCH
Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
MANUEL D'INSTALLATION
Veuillez lire le manuel d'installation en entier avant d'installer ce climatiseur pour éviter tout accident et vous assurer d'une utilisation correcte.
INSTALLATIEHANDLEIDING
Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert.
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente questo manuale di installazione prima di installare il condizionatore d'aria.
ΕΓΧΕΙΡΙΔΙΟ ΟΔΗΓΙΩΝ ΕΓΚΑΤΑΣΤΑΣΗΣ
Για ασφάλεια και σωστή χρήση, παρακαλείστε διαβάσετε προσεχτικά αυτό το εγχειρίδιο εγκατάστασης πριν αρχίσετε την εγκατάσταση της μονάδας
κλιματισμού.
MANUAL DE INSTALAÇÃO
Para segurança e utilização correctas, leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado.
INSTALLATIONSMANUAL
Læs venligst denne installationsmanual grundigt, før De installerer airconditionanlægget, af hensyn til sikker og korrekt anvendelse.
INSTALLATIONSHANDBOK
Läs den här installationshandboken noga innan luftkonditioneringsenheten installeras, för säker och korrekt användning.
MONTAJ ELKİTABI
Emniyetli ve doğru biçimde nasıl kullanılacağını öğrenmek için lütfen klima cihazını monte etmeden önce bu elkitabını dikkatle okuyunuz.
РЪКОВОДСТВО ЗА МОНТАЖ
За безопасна и правилна употреба, моля, прочетете внимателно това ръководство преди монтажа на климатизатора.
PODRĘCZNIK INSTALACJI
W celu bezpiecznego i poprawnego korzystania należy przed zainstalowaniem klimatyzatora dokładnie zapoznać się z niniejszym podręcznikiem
instalacji.
INSTALLASJONSHÅNDBOK
For sikker og riktig bruk, skal du lese denne installasjonshåndboken nøye før du installerer klimaanlegget.
РУКОВОДСТВО ПО УСТАНОВКЕ
Для осторожного и правильного использования прибора необходимо тщательно ознакомиться с данным руководством по установке до
выполнения установки кондиционера.
PŘÍRUČKA K INSTALACI
V zájmu bezpečného a správného používání si před instalací klimatizační jednotky důkladně pročtěte tuto příručku k instalaci.
NÁVOD NA INŠTALÁCIU
Pre bezpečné a správne použitie si pred inštalovaním klimatizačnej jednotky, prosím, starostlivo prečítajte tento návod na inštaláciu.
TELEPÍTÉSI KÉZIKÖNYV
A biztonságos és helyes használathoz, kérjük, olvassa el alaposan ezt a telepítési kézikönyvet, mielőtt telepítené a légkondicionáló egységet.
PRIROČNIK ZA NAMESTITEV
Za varno in pravilno uporabo pred namestitvijo klimatske naprave skrbno preberite priročnik za namestitev.
MANUAL CU INSTRUCŢIUNI DE INSTALARE
Pentru o utilizare corectă şi sigură, vă rugăm să citiţi cu atenţie acest manual înainte de a instala unitatea de aer condiţionat.
PRIRUČNIK ZA UGRADNJU
Radi sigurne i ispravne uporabe, temeljito pročitajte ovaj priručnik prije ugradnje klimatizacijskog uređaja.
安装手册
为了安全和正确地使用本空调器,请在安装前仔细阅读本安装手册。
<ORIGINAL>

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric CMB-WM350F-AA

  • Page 1 <ORIGINAL> Air-Conditioners For Building Application INDOOR UNIT CMB-WM350F-AA, CMB-WM500F-AA CMB-WM108V-BB, CMB-WM1016V-BB INSTALLATION MANUAL For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit. INSTALLATIONSHANDBUCH Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
  • Page 2 *1 Dimensions with which pipe connection can be handled at site 1210 <B> <B> [Fig. 2.4.1] CMB-WM350F-AA + CMB-WM108V-BB (CMB-WM500F-AA) (CMB-WM1016V-BB) Notes: *1 Indoor units that are connected to the same branch joint cannot be simultaneously operated in different operation modes.
  • Page 3 [Fig. 4.1.2] Unit model Model name High pressure side Low pressure side PURY-(E)M200 ø15.88 (Brazing) ø19.05 (Brazing) PURY-(E)M250 ø15.88 (Brazing) ø22.2 (Brazing) (HBC) CMB-WM350F-AA PURY-(E)M300 ø15.88 (Brazing) ø22.2 (Brazing) PURY-(E)M350 ø15.88 (Brazing) ø28.58 (Brazing) PURY-(E)M400 ø19.05 (Brazing) ø28.58 (Brazing) (HBC) PURY-(E)M450 ø19.05 (Brazing)
  • Page 4 [Fig. 4.2.1] A Cut here B Remove brazed cap [Fig. 4.3.1] A Locally procured insulating material for pipes B Bind here using band or tape. C Do not leave any opening. D Lap margin: more than 40 mm E Insulating material (field supply) F Unit side insulating material [Fig.
  • Page 5 [Fig. 5.1.1] A Expansion vessel (field supply) B Shutoff valve (field supply) To A C Strainer (field supply) D Pressure reducing valve (field supply) E Water inlet F Refrigerant pipes G Pressure gauge (field supply) H Check valve (field supply) Note: *1.
  • Page 6 [Fig. 5.1.5] Pipe size between Main-HBC and Sub-HBC *1 Pipe size between Main-HBC and indoor unit *1 Total down-stream indoor unit capacity Pipe size between Sub-HBC and indoor unit *1 Max 20 m *2 Max 40 m *2 Max 60 m *2 W/WP/WL10 I.D.
  • Page 7 C Do not leave any opening. D Lap margin: more than 40 mm E Insulating material (field supply) F Unit side insulating material [Fig. 6.0.1] CMB-WM350F-AA,CMB-WM500F-AA A Control box B Power source wiring C ø21 hole (closed rubber bushing) D Transmission wiring...
  • Page 8: Table Of Contents

    • Always use accessories specified by Mitsubishi Electric. - If a different refrigerant or air is mixed with the original refrigerant, the - Ask an authorized technician to install the accessories. Improper installation by refrigerant cycle may malfunction and the unit may be damaged.
  • Page 9: Precautions For Devices That Use R32 Refrigerant

    - If the pressure switch, thermal switch, or other protection device is shorted or private power generator, high-frequency medical equipment, or radio operated forcibly, or parts other than those specified by Mitsubishi Electric are communication equipment may cause the air conditioner to operate used, fire or explosion may result.
  • Page 10: Selecting An Installation Site

    • Indoor units that are all WP, all W, or all WL models are connectable to the HBC. 1. CMB-WM350F-AA + CMB-WM108V-BB • Piping for systems using R32 may be different from that for systems using...
  • Page 11: Installing The Hbc

    The following items are supplied with each HBC. function correctly. Model name Installing hanging bolts for Sub-HBC CMB-WM350F-AA Install locally procured hanging bolts (threaded rod) following the procedure given in CMB-WM500F-AA the figure. The hanging bolt size is ø10 (M10 screw).
  • Page 12: Refrigerant Piping Work

    4.4. Additional refrigerant charge A To outdoor unit B End connection (brazing) C Main-HBC D Sub-HBC Notes: E Indoor unit F Branch joint (field supply) • Charge refrigerant in a liquid state. G Junction pipe (field supply) H Connecting indoor unit less than 80 •...
  • Page 13 <Example> <Example> Outdoor unit model: PURY-EM300YNW-A1 Outdoor unit model: PURY-EM300YNW-A1 Main-HBC model: CMB-WM350F-AA Main-HBC model: CMB-WM350F-AA Sub-HBC model: CMB-WM108V-BB x 3 Sub-HBC model: CMB-WM108V-BB x 3 * Refer to the pipe connection examples in [Fig. 2.4.1] (P.2).
  • Page 14: Drain Piping Work

    4.5. Drain piping work • Connect the supplied drain hose to the discharge port on the unit body. Use hard vinyl chloride pipes VP-25 (ø32) for drain piping (2). Tighten the supplied drain 1. Drain piping work for Main-HBC hose onto the discharge port using the supplied hose band. (For this, do not use •...
  • Page 15 I Pressure control valve (field supply) Unit model Water volume J Auto air vent valve (Highest point on the water pipe for each branch) CMB-WM350F-AA (field supply) K Auto air vent valve (Top position of piping on Main-HBC) (field supply) CMB-WM500F-AA...
  • Page 16: Water Pipe Insulation

    5.3. Water treatment and quality control • When the junction pipes are connected to 16 Sub-HBC ports, the branched sides of the junction pipes cannot be connected to the ports "4 and 5," "8 and 9," or "12 To preserve water quality, use the closed type of water circuit. When the circulating and 13"...
  • Page 17: Electrical Work

    6. Electrical work  Consult all related regulations and power companies beforehand. Use non-polarized 2-wire as transmission cables. Use 2-core shielding cables (CVVS, CPEVS) of more than 1.25 mm in diameter as Warning: transmission cables. Electrical work should be handled by qualified electrical engineers in The switch capacity of the main power to HBC/Sub-HBC and the wire size are as accordance with all related regulations and attached instruction manuals.
  • Page 18: Debris Removal Operation

    8.2. Debris removal operation This operation removes the debris that may have been introduced during installation from the water circuit. Perform this operation after completion of the following. Automatic air vent • Water piping work valve • Air-tightness test of water piping •...
  • Page 19 2. Debris removal operation [When an outdoor unit is connected, and refrigerant piping work, evacuation of refrigerant circuits, and refrigerant charging have been completed] 1. Turn on DIP SW002-1 if there is a possibility that the debris may have been introduced into the water circuits during piping work on site. Use DIP SW002-1 to start the debris removal operation.
  • Page 20 4. Turn on DIP SW002-6. Then, slowly turn the water vent screw of the two water pumps at the lower part inside the HBC. (Maximum of two turns) Water vent screw (Maximum of two turns) Water pump (water vent screw position) Slowly open the strainer inside the HBC (on the maintenance side).
  • Page 21: Air Vent Operation

    8.3. Air vent operation This operation removes the air from the water circuit after water is supplied to it. Perform this operation after completion of the following. Automatic air vent • Water piping work valve • Air-tightness test of water piping •...
  • Page 22 2. Air vent operation [When an outdoor unit is connected, and refrigerant piping work, air-tightness test of refrigerant piping, evacuation of refrigerant circuits, and refrigerant charging have been completed] 1. Turn on DIP SW002-3 of the Main-HBC. 2. The LED on the control board indicates "Air1," "Air2," "Air3," "Air 4," and "AirE" in order, and the pump will stop after a while. Total estimated time for air vent operation LED position DIP SW position...
  • Page 23 Flowchart for air vent operation (Turn on DIP SW002-3.) The operation is performed to Air 1 Intermittent operation of water pump (20 min) discharge air from the water circuits. [Air1] Supplying water to all indoor units Air 2 Water supply to all indoor units (20 min) lightly removes the air from the system.
  • Page 24 Date of manufacture is indicated in format «yyyy.mm» in the «YEAR OF MANUFACTURE» field on the nameplate.
  • Page 25 CMB-WM350~500F-AA Model Name of Motor P722167X01(CHLF4-20LSLSC) Item (3) Manufacturer’s name or trade mark, commercial registration number and address MITSUBISHI ELECTRIC CORPORATION AIR-CONDITIONING & REFRIGERATION SYSTEMS WORKS 5-66, Tebira 6 Chome, Wakayama-City 640-8686, Japan (4) Product’s model identifier CMB-WM350~500F-AA (12) If the motor is considered exempt from efficiency requirement , the specific reason why it is considered exempt.
  • Page 26 nome o marchio, numero di iscrizione nel registro delle imprese e sede del fabbricante; identificativo del modello del prodotto; se il motore è considerato esente dalla specifica di efficienza ai sensi dell’articolo 2, paragrafo 2, del presente regolamento, la ragione per cui è considerato esente. a)motori completamente integrati in un prodotto (ad esempio in un cambio, una pompa, un ventilatore o un compressore) per i quali non è...
  • Page 28 Please be sure to put the contact address/telephone number on this manual before handing it to the customer. HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN MANUFACTURER: MITSUBISHI ELECTRIC CORPORATION Air-conditioning & Refrigeration Systems Works 5-66, Tebira 6 Chome, Wakayama-city, 640-8686, Japan WT09805X01_en...
  • Page 29 Related Links Model Number: CMB-WM1016V-BB CMB-WM-F(V)-AA(B)_InstallationManual_WT09805X01 CMB-WM-F-AA_ServiceHandbook_HWE21050 HVRF_Information_Pack_Ver1.0_ Vertical & Horizontal HBC Databook (MEES21K003)

This manual is also suitable for:

Cmb-wm500f-aaCmb-wm108v-bbCmb-wm1016v-bb

Table of Contents