[3-3 Functions of the Major Components of Outdoor Unit ]

3-3

Functions of the Major Components of Outdoor Unit

Part
Symbols
name
(functions)
Com-
MC1
pressor
(Comp1)
High
63HS1
pres-
sure
sensor
Low
63LS
pres-
sure
sensor
Pres-
63H1
sure
switch
Thermis-
TH4
tor
(Discharge
temperature)
14
- chapter 3
Notes
Usage
Adjusts the amount of circulating
refrigerant by adjusting the operat-
ing frequency based on the oper-
ating pressure data
1) Detects high pressure
2) Regulates frequency and pro-
vides high-pressure protec-
tion
1) Detects low pressure
2) Provides low-pressure pro-
tection
1) Detects high pressure
2) Provides high-pressure pro-
tection
1) Detects discharge air tem-
perature
2) Provides high-pressure pro-
tection
0°C[32°F] : 698 kΩ
10°C[50°F] : 413 kΩ
20°C[68°F] : 250 kΩ
30°C[86°F] : 160 kΩ
40°C[104°F] : 104 kΩ
50°C[122°F] : 70 kΩ
60°C[140°F] : 48 kΩ
70°C[158°F] : 34 kΩ
80°C[176°F] : 24 kΩ
90°C[194°F] : 17.5 kΩ
100°C[212°F] : 13.0 kΩ
110°C[230°F] : 9.8 kΩ
Specifications
(E)M200 - (E)M350 models
Low-pressure shell scroll
compressor
wirewound resistance
20°C [68°F] : 0.192Ω
(E)M400 - (E)M500 models
Low-pressure shell scroll
compressor
wirewound resistance
20°C [68°F] : 0.219Ω
Pressure
63HS1
0~4.15 MPa [601psi]
Vout 0.5~3.5V
1 2 3
0.071V/0.098 MPa [14psi]
Pressure [MPa]
Con-
=1.38 x Vout [V]-0.69
nector
Pressure [psi]
=(1.38 x Vout [V] - 0.69) x 145
1
GND (Black)
2
Vout (White)
3
Vcc (DC5V) (Red)
Pressure
63LS
0~1.7 MPa [247psi]
Vout 0.5~3.5V
1 2 3
0.173V/0.098 MPa [14psi]
Pressure [MPa]
Con-
=0.566 x Vout [V] - 0.283
nector
Pressure [psi]
=(0.566 x Vout [V] - 0.283) x 145
GND (Black)
1
2
Vout (White)
3
Vcc (DC5V) (Red)
4.15MPa[601psi] OFF set-
ting
Degrees Celsius
R
= 7.465k
120
R
= 4057
25/120
R =
t
1
1
7.465
exp
4057
393
Check method
Resistance check
BS_03_L

Hide quick links:

Advertisement

loading