Connecting the heating elements and three-phase line
supply (PM4220 Highend: see figure 4/5,
POM4220 Flexible: see figure 6/7)
The heating elements are connected by means of two plug
connectors at X1 and X3 of the POM:
The 3-phase line is connected by means of one 3-pin plug
connector at X2 of the POM.
Note
The plug connectors for the heating elements and the power
connection are included in the scope of delivery of the
heating control system.
Features: Spring-type terminal and automatic tool-free
interlock or screwed joint (phase connection). To unlock,
press down the two levers on the sides of the plug
connectors.
To lock the plug connector in place correctly, press it in by
the plug body and not by the gray unlatching wedge.
NOTICE
The connected loads (heating elements) must not exceed
the maximum permissible current of 50 A per phase.
Pin assignment X1 to X3
X1 POM4220 Highend: 4-pole plug for
power outputs 1 ... 4
POM4220 Flexible: 6-pole plug for
power outputs 1 ... 6
X2 3-pin connector for line connection
phase LX1, N, LX3
X3 POM4220 Highend: 4-pole plug for
power outputs 5 ... 8
POM4220 Flexible: 6-pole plug for
power outputs 7 ... 12
Technical specifications
Connection data for POM4220 Highend /
POM4220 Flexible
Rated operating voltage
Number of output channels
4
POM4220 Highend:
230/277 V AC,
400/480 V AC
POM4220 Flexible:
45 V AC, 75 V AC,
110 V AC, 230/277 V AC
POM4220 Highend: 8
POM4220 Flexible: 12
Maximum switching
capacity per output channel
Fuse for each output
channel
Total switching capacity of
the device
Overvoltage category
Power supply
Voltage
Active power drawn,
maximum
Ambient conditions
Ambient temperature in
operation
Ambient temperature during
storage and transport
Relative air humidity during
operation and storage
Degree of pollution
Maximum height above sea
level
Mechanical specifications
Weight
Degree of protection
Dimensions (W x H x D)
Technical Assistance
Telephone: +49 (0) 911-895-7222 (8°° - 17°° CET)
Email: technical-assistance@siemens.com
Internet: www.siemens.com/automation/support-request
Additional documentation
You will find further information (e.g. on parameterization,
service, etc.) in Siemens Industry Online Support
(http://support.automation.siemens.com/WW/view/en/10807
371/133300).
POM4220 Highend:
- 5540 W / 277 V
- 9600 W / 480 V
POM4220 Flexible:
- 4432 W / 277 V
Melting fuse (internally
accessible)
- POM4220 Highend: 25 A
- POM4220 Flexible: 16 A
POM4220 Highend:
48 kW / 480 V
POM4220 Flexible:
27.7 kW / 277 V
Category III
24 V DC (± 20%), via CIM
1 W
0 °C to 55 °C
-25 °C to +70°C
95 % at 25 °C, decreasing
linearly to 50 % at 50 °C
2
2000 m
Approx. 1.5 kg
IP20
36 mm x 285 mm x 281 mm
POM4220 Highend / Flexible
A5E42873959A/002, 11/2017

Advertisement

loading

This manual is also suitable for: