Base Specifications; Detector Specifications; Electrical Supervision - Bosch F220 Series Installation Manual

Hide thumbs Also See for F220 Series:
Table of Contents

Advertisement

F220 Series Detectors with F220-B6/C/E/R Bases
2.3.2

Base Specifications

Alarm Current (only base current, detector current excluded)
Standby Current
Voltage
Table 2.4 F220-B6 Series Base Specifications
2.3.3

Detector Specifications

Current
Powerup Time
Rate of Rise
Voltage
Table 2.5 F220 Series Detector Heads Specifications
2.4

Electrical Supervision

When the F220-B6 Series Bases are wired according to the
instructions in this document, the control panel initiates a
trouble signal when a detector is removed from its base,
Bosch Security Systems, Inc.
F220-B6:
F220-B6C:
F220-B6E:
F220-B6R:
F220-B6/C/R:
F220-B6E:
F220-B6 (two-wire):
F220-B6C/E/R (four-wire): 10.0 VDC to 30.0 VDC
Alarm:
20 mA minimum at 8.5 VDC
35 mA maximum at 32 VDC
Standby:
0.12 mA maximum
Startup:
0.12 mA maximum
22 second maximum
F220-135:
15°F/min (9°C/min) or greater
Operating:
8.5 VDC to 32.0 VDC
RMS Ripple:
25% of DC input
Installation Manual
General Information | en 9
Two-wire base; no base current
31 mA at 12 VDC
35 mA at 24 VDC
40 mA maximum at 30 VDC
25 mA at 12 VDC
30 mA at 24 VDC
34 mA maximum at 30 VDC
13.5 mA at 12 VDC
16.5 mA at 24 VDC
19 mA maximum at 30 VDC
No current draw in standby
16 mA maximum at 30 VDC
8.5 VDC to 32.0 VDC
4998138694 -04 | 2007.01

Advertisement

Table of Contents
loading

This manual is also suitable for:

F220-b6F220-cF220-eF220-r

Table of Contents