364xS User's Manual
On
to start the Totalizer
to stop the Totalizer
Off
In case the Totalizer is used in Bidirectional Flow mode the Totalizer LRV (0%) and the Totalizer URV
(100%) have to be equal in absolute value. If different the Totalizer Status remains OFF.
Digital LCD Integral Display Keys sequence to operate the Totalizer Status: 4 - 1 - Edit
To reset the Permanent Totalizer
Navigate the Digital LCD Integral Display menu, select
reset select
OK.
Digital LCD Integral Display Keys sequence to reset the Permanent Totalizer: 4 – 2 – 1 - OK
To reset the Batch Totalizer
Navigate the Digital LCD Integral Display menu, select
select
OK.
Digital LCD Integral Display Keys sequence to reset the Batch Totalizer: 4 – 2 – 2 - OK
To protect the Permanent Totalizer
Navigate the Digital LCD Integral Display menu, select
Protection,
and the actual protection will be available (Unlock and Lock). To modify select
desired protection with the up and down keys and confirm with
Digital LCD Integral Display Keys sequence to protect the Permanent Totalizer: 4 – 2 – 1 – 2 - Edit
To change the Permanent Totalizer protection Password:
The Permanent Totalizer Password is a five digit string. The default value, at the transmitter delivery is
. When this default password is set the protection does not work.
Navigate the Digital LCD Integral Display menu, select
Password, and the actual password will be available. To modify select
alphanumeric symbol with the up and down keys and confirm with
digits and confirm with
OK.
Digital LCD Integral Display Keys sequence to change the Permanent Totalizer Password: 4 – 2 – 1 – 3 – Edit

Totalizer operation by HHT

Totalizer operation by Hand Held Terminal is available. Please refer to the device manual for the
appropriated operations.

Totalizer operation by PC

Totalizer operation by PC is available using dedicated Software. ABB can provide the references and the
Software. Please refer to the Software instructions for the appropriated operations.

Reset to Factory trim

The transmitter has in the memory the Sensor Low trim, the Sensor High trim and the Output trimming
(Digital to analog trim) defined or calculated during the transmitter assembly. These data have been defined
as Factory trim.
The Reset to Factory trim allow the restoration of the as-shipped factory settings of the sensor trim and
analog output trim.
The Reset to Factory trim is suggested in case wrong trim operations are performed and the transmitter is in
an undefined condition (i.e.: inadvertent zero trim of an absolute pressure unit or inaccurate pressure
source).
NOTE
Totalizer
>
Reset
>
Permanent Totalizer
Totalizer
>
Reset
>
Batch Totalizer
Totalizer
>
Reset
OK.
Totalizer
>
Reset
>
Next.
Repeat the operation for the five
> Reset. To
> Reset. To reset
>
Permanent Totalizer
Edit
then scroll the
Permanent Totalizer
>
Change
Edit
then scroll the desired
Operation
53
>
Tot.