364xS User's Manual
"Ex Safety" Aspects for North America
According to Factory Mutual Standards which can assure compliance with Essential Safety Requirements
FM 3600 :
Electrical Equipment for use in Hazardous (Classified) Locations, General Requirements.
FM 3610 :
Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, III, Division 1, and
Class I, Zone 0 & 1 Hazardous (Classified) Locations.
FM 3611 :
Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III Division 1
and 2 Hazardous (Classified) Locations.
FM 3615 :
Explosionproof Electrical Equipment.
FM 3810 :
Electrical and Electronic Test, Measuring and Process Control Equipment.
NEMA 250 : Enclosure for Electrical Equipment (1000 Volts Maximum)
The 364 pressure transmitter models have been certified by Factory Mutual for the following Class, Divisions
and Gas groups, hazardous classified locations, temperature class and types of protection.
Explosionproof for Class I, Division 1, Groups A, B, C and D, hazardous (classified) locations.
Dust Ignition proof for Class II, III Division 1, Groups E, F and G, hazardous (classified) locations.
Suitable for Class II, III, Division 2, Groups F and G, hazardous (classified) locations.
NonIncendive for Class I, Division 2, Groups A, B, C and D, in accordance with Nonincendive field
wiring requirements for hazardous (classified) locations.
Intrinsically Safe for use in Class I, II and III, Division 1, Groups A, B, C, D, E, F, and G in accordance
with Entity requirements for hazardous (classified) locations.
Temperature class T4 to T6 (dependent on the maximum input current and the maximum ambient
temperature).
Ambient Temperature range -50°C to +85°C (dependent on the maximum input current and the
maximum temperature
class).
Electrical Supply range Minimum 10.5 Volts, Maximum 42 Volts (dependent on the type of protection,
maximum ambient
Temperature, maximum temperature class and communication protocol).
Type 4X applications Indoors/Outdoors.
The 364 pressure transmitter models installed in Explosionproof Class 1 Division 1 Group A, B, C
and D hazardous (classified) location does not require conduit sealing as per
For a correct installation in field of the 364 pressure transmitter models please see the related control
drawing.
Note that the associated apparatus must be FM approved.
NOTE
FM 3615 sect 4.3 / NEC 501.15.
66
Additional Safety