TZIDC DIGITAL POSITIONER | CI/TZIDC/C-FM-US-EN REV. A
... 2 Use in potentially explosive atmospheres

cFMus

Ex marking

TZIDC without mechanical position indication
Model number: V18345-10b2c2de0f or V18345-30b2c2de0f
IS / I, II, III / 1 / ABCDEFG / T6, T4 Ta = 40°C, 85°C - 901265; Entity
NI / I, II, III / 2 / ABCDEFG / T6, T4 Ta = 40°C, 85°C
Type 4X; IP65
Max Entity Parameters: Per Control Drawings
Certificate
FM20US0122X und FM20CA0061X
TZIDC with mechanical position indication
Model number: V18345-20b2c2de0f or V18345-40b2c2de0f
IS / I / 1 / ABCD / T6, T4 Ta = 40°C, 85°C - 901265; Entity
IP65
Max Entity Parameters: Per Control Drawings
Certificate
FM20US0122X und FM20CA0061X
Model number details
b Set input / communication port: 1 or 2.
c
Set output / safety position: 1, 2, 4 or 5.
d Optional upgrade with plug-in module for analog / digital
feedback (option): 0, 1, 3 or 5.
e
Optional upgrade with mechanical digital feedback (option):
0, 1 or 2.
f
Design (painting / marking): 1, H, P, S or 2

Temperature Data

Temperature class
Ambient temperature Ta
T4 T125 °C
−40 °C < Ta < 85 °C
T6 T85 °C
−40 °C < Ta < 40 °C

Electrical Data

Refer to FM installation drawing No. 901265 on page 10.

Commissioning, installation

The ABB positioner has to be mounted in a major system.
Depending on the degrees of IP-protection, an interval for
cleaning the equipment (dust settlement) has to be defined.
Strict care has to be taken that only such equipment is installed
that complies with the types of protection relevant to the
applicable zones and categories. When installing the equipment,
the locally applicable rules on erection, e.g. EN 60079-14, have to
be observed.
Other important facts to be observed:
In all zones, the circuits of the positioner have to be put
into service by a person qualified according to TRBS 1203.
The details on the type label are mandatory for doing this.
The equipment is constructed for IP 66 and has to be
protected accordingly in adverse ambient conditions.
The EC-Type Examination Certificates have to be taken
into account including any special conditions defined
therein.
The equipment shall only be used as intended.
The equipment is only to be connected when de-
energized.
The potential equalization of the system has to be
established according to the regulations of erection
applicable in the respective country of use (VDE 0100,
part 540; IEC 364-5-54). For installation according to the
North American Zone concept the external grounding is
supplementary.
Circulating currents shall not be led via the enclosures!
It has to be ensured that the enclosure is properly
installed and that its IP protection is not impaired.
Inside the potentially explosive atmospheres' assembly
shall only be performed taking the locally applicable rules
of erection into account.
The following conditions have to be observed (incomplete):
Assembly and maintenance to be done only if atmosphere
is Ex-free and a permit for hot works is in place.
The TZIDC is only to be operated in a fully mounted and
intact enclosure.