Connection On Device - Tzidc Control Unit With Tzidc Remote Sensor - ABB TZIDC Manual

Digital positioner
Table of Contents

Advertisement

30
TZIDC DIGITAL POSITIONER | CI/TZIDC/C-FM-US-EN REV. A
... 5 Installation
... Electrical connections

Connection on device - TZIDC Control Unit with TZIDC Remote Sensor

TZIDC Control Unit
1 Terminals TZIDC Remote Sensor
2 Terminals for mechanical digital feedback
Figure 20: Connection of TZIDC Control Unit with TZIDC Remote Sensor (example)
In the case of the 'TZIDC Control Unit with TZIDC Remote Sensor'
design, the components are supplied in two housings, which
together form one harmonized unit.
Housing 1 (TZIDC Control Unit) contains the electronics and
pneumatics along with the following options (where applicable):
Plug-in module for analog feedback
Plug-in module for digital feedback
Housing 2 (TZIDC Remote Sensor) contains the position sensor
and is suitable for mounting on linear or part-turn actuators.
If necessary, the following options can be installed if required:
Optical position indicator
Mechanical digital feedback with proximity switches or
microswitches.
Connect the positioner (TZIDC Control Unit, housing 1) and
remote position sensor (TZIDC Remote Sensor, housing 2) while
following the instructions below:
The sensor and the electronics have been matched.
Ensure that only devices with the same serial number are
connected.
3 EMC Cable gland
4 Shielded connection cable
A shielded 3-wire cable with a maximum length of 10 m
(33 ft) must be used for the connection.
Route the cable into the terminal compartment through
the EMC cable glands. Ensure that the shielding is
secured correctly in the EMC cable glands.
Connect the cables in accordance with the electrical
connections and tighten the screws of the terminals so
that they are hand-tight.
The electrical connection of the TZIDC Control Unit and
the optional modules are described in Positioner /
TZIDC Control Unit Electrical Connection on page 24.
If the TZIDC Control Unit is fastened so that it is it non-
conductive, the housing must be grounded (TZIDC
Control Unit and TZIDC Remote Sensor housing with the
same electric potential); otherwise control deviations
could occur with regard to analog position feedback.
Use wire end ferrules when connecting.