Electrical connections
4.4.1

Electrical connection of TZIDC with remote position sensor

TZIDC control unit
1
2
3
Fig. 21
1 Analog position feedback
2 Digital position feedback switch 1
3 Digital position feedback switch 2
4 Connecting cable for remote position sensor
5 Connecting cable for remote position sensor
6 Connecting cable for remote position sensor
IMPORTANT (NOTE)
The sensor and the electronics have been carefully matched. Therefore, during installation,
please make sure that devices are only connected if they have the same serial number.
Connect the connecting cable shield to both housings using EMC cable glands.
The pneumatic outputs must be connected to the drive using cables at least 6 mm in diameter.
If the control unit is attached so that it is it non-conductive, the housing must be grounded
(control unit and remote sensor housing at same electrical level); otherwise, control deviations
could occur with regard to analog position feedback.
26
4
5
6
7
8
9
10
7 Binary output
8 Binary input
9 Setpoint input
10 Ground connection
11 Proximity switches/Microswitches, switch 1
12 Proximity switches/Microswitches, switch 2
TZIDC, TZIDC-110, TZIDC-120
TZIDC remote sensor
CI/TZIDC/110/120-EN
11
12
10
M00759