TZIDC DIGITAL POSITIONER | OI/TZIDC-EN REV. B
... 6 Installation
... Electrical connections
Connection on device – TZIDC Control Unit for remote position sensor
M 20 mm /
NPT
1/2"
3
1 Terminals for remote position sensor
2 Remote position sensor
Figure 23: Connection of TZIDC Control Unit with remote position sensor (example)
Change from one to two columns
With the TZIDC designed for remote position sensors, the
positioner is supplied without a position sensor.
The TZIDC Control Unit contains the electronics and pneumatics
along with the following options (where applicable):
Analog position feedback
Digital position feedback
Any position sensor (4 to 30 k , with line break detection
4 to 18 k ) can be connected.
1
M 20 mm /
NPT
1/2"
4
3 EMC Cable gland
4 Shielded connection cable
Connect the positioner (TZIDC Control Unit) and remote
position sensor while observing the following instructions:
A shielded 3-wire cable with a maximum length of 10 m (33 ft)
must be used for the connection.
Route the cable into the terminal compartment through the
EMC cable glands. Ensure that the shielding is secured
correctly in the EMC cable glands.
Connect the cables in accordance with the electrical
connections and tighten the screws of the terminals so that
they are hand-tight.
The electrical connection of the TZIDC Control Unit and the
optional modules are described in Positioner /
TZIDC Control Unit Electrical Connection on page 22.
If the TZIDC Control Unit is fastened such that it is it non-
conductive, the housing must be grounded (TZIDC Control
Unit and remote position sensor housing with the same
electric potential); otherwise control deviations could occur
with regard to analog position feedback.
Use wire end ferrules when connecting.