Fm / Csa; Csa International - ABB TZIDC Operating Instructions Manual

Digital positioner
Table of Contents

Advertisement

10
TZIDC DIGITAL POSITIONER | OI/TZIDC-EN REV. B
... 2 Use in potentially explosive atmospheres

FM / CSA

(limited functionality)

CSA International

Certificate
Certificate
Class 2258 02
Class 2258 04
Electric data
Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner
For use in
Input rated
Max output pressure
Max. ambient temperature
Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner intrinsically safe
with entity parameters of:
For use in
Terminals 11 / 12
Terminals 81 / 82
Terminals 83 / 84
Terminals 31 / 32
Terminals 41 / 42 and 51 / 52
Terminals Limit 2 41 / 42
and Limit 1 51 / 52
1052414
PROCESS CONTROL EQUIPMENT – For
Hazardous Locations
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For Hazardous
Locations
Class I, Div 2, Groups A, B, C and D
Class II, Div 2, Groups E, F, and G
Class III, Enclosure Type 4X
30 V DC; max. 4 to 20 mA
80 psi (Marine version)
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F and G
Class III, Enclosure Type 4X:
U
= 30 V
C
= 6.6 nF
max
i
I
= 104 mA
L
max
U
= 30 V
C
= 4.2 nF
max
i
I
= 110 mA
L
max
U
= 30 V
C
= 4.2 nF
max
i
I
= 90 mA
L
max
U
= 30 V
C
= 6.6 nF
max
i
I
= 110 mA
L
max
U
= 30 V
C
= 3.7 nF
max
i
I
= 96 mA
L
max
U
= 15.5 V
C
max
i
I
= 52 mA
L
= 30 μH
max
i
Note
The 'x' in P/N denotes minor mechanical variations or
optional features.
Local communication interface (LCI) shall not be used in
hazardous location.
Each pair of conductors of each intrinsic safety circuit shall
be shielded.
See FM installation drawing No. 901064 for Details.
90 psi
85 °C
= 0 μH
i
= 0 μH
i
= 0 μH
i
= 0 μH
i
= 0 μH
i
= 20 nF

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents