Operating Modes; Standard Automatic Adjustment; Standard Automatic Adjustment For Linear Actuators; Standard Automatic Adjustment For Rotary Actuators - ABB TZIDC Operating Instructions Manual

Digital positioner
Table of Contents

Advertisement

TZIDC DIGITAL POSITIONER | OI/TZIDC-EN REV. B

Operating modes

Selection from the operating level
1. Press and hold down MODE.
2. Also press and release
selected operating mode is displayed.
3. Release MODE.
The position is displayed in % or as a rotation angle.
Operating mode
Mode indicator
1.0
Control mode* with
adaptation of the control
parameters
1.1
Control mode* without
adaptation of the control
parameters
1.2
Manual adjustment** in
the operating range.
Adjust*** using
or
1.3
Manual adjustment** in
the measuring range.
Adjust*** using
or
*
Since self-optimization in operating mode 1.0 is subject to several factors
during control operation with adaptation, incorrect adjustments could
appear over an extended period.
** Positioning not active.
*** For high-speed mode, press
rapidly as often as required. The
Position indicator
M10906a
M10906b
M10906c
M10906d
and
simultaneously.

Standard automatic adjustment

Note
Standard Auto Adjust does not always result in optimum control
conditions.

Standard automatic adjustment for linear actuators*

1. MODE Press and hold until ADJ_LIN is displayed.
2. MODE Press and hold until the countdown ends.
3. Release MODE; this starts Autoadjust.

Standard automatic adjustment for rotary actuators*

1. ENTER Press and hold until ADJ_ROT is displayed.
2. ENTER Press and hold until the countdown ends.
3. Release ENTER; this starts Autoadjust.
M10906f
If Autoadjust is successful, the parameters will be stored
automatically and the positioner will revert to operating
mode 1.1.
M10906g
If an error occurs during Autoadjust, the process will be
terminated with an error message.
M10906g
Perform the following steps if an error occurs:
1. Press and hold down operating button
approximately three seconds.
The unit will switch to the operating level, mode 1.3 (manual
adjustment within the measuring range).
M10906h
M10906h
2. Check mechanical mounting in accordance with Mechanical
mounting on page 16 and repeat the standard automatic
adjustment.
*
The zero position is determined automatically and saved during standard
automatic adjustment, counter-clockwise (CTCLOCKW) for linear actuators
and clockwise (CLOCKW) for rotary actuators.
31
or
for

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents