TZIDC DIGITAL POSITIONER | OI/TZIDC-EN REV. B
Parameter description HART®
Parameter Display
Function
P1._
STANDARD
P1.0
ACTUATOR
Actuator type
P1.1
AUTO_ADJ
Automatic adjustment Autoadjust
P1.2
ADJ_MODE
Auto adjust mode
P1.3
TEST
Test
P1.4
FIND_DEV
Find device
P1.5
EXIT
Return
P2._
SETPOINT
P2.0
MIN_RGE
Min setpoint range
P2.1
MAX_RGE
Max setpoint range
P2.2
CHARACT
Charact. curve
P2.3
ACTION
Valve action
P2.4
SHUT_CLS
Shut-off value 0%
P2.5
SHUT_OPN
Shut off value 100%
P2.6
RAMP UP
Set point ramp, up
P2.7
RAMP DN
Set point ramp, down Setpoint ramp (down)
P2.8
EXIT
Return
P3._
ACTUATOR
P3.0
MIN_RGE
Min. of stroke range
P3.1
MAX_RGE
Max. of stroke range
P3.2
ZERO_POS
Zero position
P3.3
EXIT
Return
P4._
MESSAGES
P4.0
TIME_OUT
Control time out
P4.1
POS_SW1
Position switch 1
P4.2
POS_SW2
Position switch 2
P4.3
SW1_ACTV
Switchpoint 1 enable
P4.4
SW2_ACTV
Switchpoint 2 enable
P4.5
EXIT
Return
P5._
ALARMS
P5.0
LEAKAGE
Leakage detection
P5.1
SP_RGE
Setpoint rng monitor
SENS_RGE
P5.2
Sens. range monitor
CTRLER
P5.3
Controller monitor
TIME_OUT
P5.4
Control time out
STRK_CTR
P5.5
Stroke counter
TRAVEL
P5.6
Travel counter
EXIT
P5.7
Return
Possible parameter setting
Actuator type
LINEAR, ROTARY
Function
Automatic adjustment mode FULL,STROKE,CTRL_PAR, ZERO_POS, LOCKED
Test
Function
Find device
DISABLE, ONE TIME, CONTINOUS
Return to operating level
Function
Min. setpoint range
4.0 to 18.4
Max. setpoint range
20.0 to 5.6
Characteristic curve
LINEAR, 1:25, 1:50, 25:1, 50:1, USERD
Direction of action
DIRECT, REVERSE
Shut-off value 0 %
OFF, 0.1 to 45.0
Shut-off value 100%
55.0 to 100.0, OFF
Setpoint ramp (up)
OFF, 0 to 200
OFF, 0 to 200
Return to operating level
Function
Operating range, min.
0.0 to 90.0
Operating range, max.
100.0 to 10.0
Zero position
CLOCKWISE, CTCLOCKWISE
Return to operating level
Function
Dead band time limit
OFF, to 200
Switching point SW1
0.0 to 100.0
Switching point SW2
0.0 to 100.0
Active direction SW1
FALL_BEL, EXCEED
Active direction SW2
FALL_BEL, EXCEED
Return to operating level
Function
Leakage to actuator
ACTIVE, INACTIVE
Outside the setpoint range
ACTIVE, INACTIVE
Operating range exceeded
ACTIVE, INACTIVE
Controller inactive
ACTIVE, INACTIVE
Dead band time limit
ACTIVE, INACTIVE
Movement counter
ACTIVE, INACTIVE
Travel counter
ACTIVE, INACTIVE
Return to operating level
Function
37
Unit
Factory setting
---
LINEAR
---
---
FULL
---
INACTIVE
---
DISABLE
---
NV_SAVE
mA
4.0
mA
20.0
---
LINEAR
---
DIRECT
%
1.0
%
OFF
---
OFF
---
OFF
---
NV_SAVE
%
0.0
%
100
---
CTCLOCKWISE
---
NV_SAVE
---
OFF
%
0.0
%
100.0
---
FALL_BEL
---
EXCEED
---
NV_SAVE
---
INACTIVE
---
INACTIVE
---
INACTIVE
---
INACTIVE
---
INACTIVE
---
INACTIVE
---
INACTIVE
---
NV_SAVE