Parameter Setting Example - ABB HART Industrial IT enabled TZIDC Operating Instructions Manual

Electro-pneumatic positioner for 4...20 ma two-wire technology
Table of Contents

Advertisement

3.4.3 Parameter setting example

IMPORTANT
"Changing zero position (of the LCD) from clockwise to counter-clockwise"
Initial situation: the positioner is operating in mode 1.1.
1. Change over to the configuration level:
-
Press and hold
-
Additionally, briefly press
-
Wait until the countdown has run down from 3 to 0.
-
Release
-
conf
2. Change over to parameter group 3._:
-
Simultaneously press and hold
-
Additionally 2 x briefly press
-
conf
-
Release
-
conf
3. Select parameter 3.2 "Zero position":
-
Press and hold
-
Additionally 2 x briefly press
-
conf
-
Release
4. Change parameter setting:
-
Briefly press
28
An overview of the parameter settings that can be edited via the front
panel keypad is found in Appendix A.
and
at the same time.
ENTER
and
.
°
C
%
is displayed.
mA
°
C
%
is displayed.
mA
and
MODE
ENTER
°
C
%
is displayed.
mA
.
MODE
°
C
%
is displayed.
mA
.
MODE
to select "CTCLOCKW".
Electro-pneumatic positioner TZIDC
.
and
MODE
ENTER
.
.
.
.
41/18-79 EN