Influence of ambient temperature
≤ 0.5 % for every 10 °C change in temperature
Influence of vibration
≤ ± 1 % up to 10 g and 80 Hz
Seismic requirements
Meets requirements of DIN/IEC 68-3-3 Class III for strong and
strongest earthquakes
Influence of mounting orientation
No effect
Meets the requirements of the following directives
EMC Directive 89/336/EEC as of May 1989
EC Directive for CE conformity marking
Communication
HART Protocol 5.1
Local connector for LKS (local communication interface) adapter
HART communication via 20 mA signal line with (optional) FSK modem
Environmental capabilities
Ambient temperature
-40 °C to +85 °C for operation, storage and transport
-25 °C to +85 °C with proximity switches SJ2-S1N (NO)
Relative humidity
Operational (with closed case and air supply switched on):
95 % (annual average), condensation permissible
Transport and storage:
75 % (annual average), non-condensing
Case
Material/Protections
Aluminum, protection class IP 65 / NEMA 4X
Surface/color
Electrostatic dipping varnish with epoxy resin, stove-hardened
Case varnished black, RAL 9005, matt, cap Pantone 420
Electrical connections
Screw terminals:
2
max. 1.0 mm
for options, max. 2.5 mm
NOTICE: Do not expose the terminals to strain!
Cable entry:
2 threads 1/2-14 NPT or M20x1.5
(1 with cable gland and 1 with pipe plug)
Pneumatic connections
Threads G 1/4 or 1/4-18 NPT
Weight
1.7 kg
Mounting orientation
any orientation allowed
Dimensions
see dimensional drawings in data sheet 10/18-0.22 EN
41/18-79 EN
2
for analog signal
Electro-pneumatic positioner TZIDC