ABB HART Industrial IT enabled TZIDC Operating Instructions Manual page 34

Electro-pneumatic positioner for 4...20 ma two-wire technology
Table of Contents

Advertisement

Safety Integrity Level
EXIDA report No.:
The positioner TZIDC and the shutdown module for TZIDC meet the requirements regarding
– functional safety in accordance with IEC 61508/IEC 61511-1
– explosion protection (depending on the model)
– electromagnetic compatibility in accordance with EN 61000
In case of a failure of electrical power or compressed air supply or when a positioner mal-
function occurs, the actuator is depressurized by the TZIDC, and the return spring in the ac-
tuator moves the valve to a pre-defined, safe end position (either OPEN or CLOSED).
SIL specific safety-related characteristics
Device
TZIDC
Shutdown module
for TZIDC
For details refer to the Management Summary in the SIL Safety Instructions 37/18-79XA
34
ABB 03/09-13 R003, Revision R1.0
Category
SFF
SIL2
85 %
SIL2
94 %
Electro-pneumatic positioner TZIDC
λdd + λs
PFDav
-4
7.52 × 10
1011 FIT
-4
1.76 × 10
718 FIT
λdu
172 FIT
40 FIT
41/18-79 EN