3
Installing and commissioning
3.1 Mechanical mounting
3.1.1 General
Fig. 2
Operating range
+30°
100%
100%
0%
0%
-30°
Fig. 3
Positioner ranges
41/18-79 EN
1
Sensor range for linear actuators
+60°
Sensor range for rotary actuators
Operating range for linear actuators
Operating range for rotary actuators
-60°
Electro-pneumatic positioner TZIDC
2
TZID-C
The arrow (1) on
the feedback shaft
(and thus the lever)
must travel within
the
area
marked
with
the
small
arrows (2).
When mounting the
positioner, ensure
that the transfer of
the stroke or rota-
tion angle for the
position feedback is
correct. The maxi-
mum rotation angle
is 60° for mounting
to linear actuators
and 120° for mount-
ing to rotary actua-
tors. The minimum
angle is always 25°.
11