1.3 Explosion protection

One of the type plates seen below is attached to the positioner to the left of the main type
plate, depending on the positioner's explosion protection. It indicates the degree of explo-
sion protection and the certificate valid for your positioner. For details please refer to
chapter "Certificates" starting on page 38.
!
WARNING
30 VDC Max / 4 - 20 mA
FM
APPROVED
T4 Tamb. = 85 °C
Class I, II, III
Div. 1, Grp. A-G
N.I. Class I, II, III
Div 2, Grp. A-G
NEMA 4X
INTRINSICALLY SAFE / SECURITE INTRINSIQUE
ABB Automation
Made in Germany
Fig. 1
Type plates indicating the degree of explosion protection

1.4 Correct use

The TZIDC positioner is an electro-pneumatic positioner with flameproof enclosure for
pneumatic final control elements. It is designed for being attached to linear and rotary
actuators following the instructions in this manual. The positioner may be used only for
the applications listed in these operating instructions or in the data sheet 18-0.22 EN.
Any other use is considered as incorrect.
The signal current circuit and the input and output circuitry must meet the explosion pro-
tection requirements stipulated in the certificates (see chapter "Certificates" starting on
page 38).
The maximum permissible ambient temperature range of -40 °C to +85 °C (when using
proximity switches of type SJ2-S1N (NO): -25 °C to + 85 °C) must not be exceeded.
41/18-79 EN
Always observe the specifications and special requirements for your
positioner stipulated in the applicable certificate.
R
Exia T4 max. 85 °C
Cl. I, Gp. A, B, C, D;
Cl. II, Gp. E, F, G; Cl. III
Cl. I, Div. 2, Gp. A, B, C, D
Cl. II, Div. 2, Gp. E, F, G
Cl. III, Div. 2
TYPE 4X
Per Control Document
No. 901064
Electro-pneumatic positioner TZIDC