Operation With Flammable Gas; Operation In Temperature Class T6; Atex And Iecex Temperature Data; Type Of Protection Ex I, Intrinsic Safety - ABB PositionMaster EDP300 Commissioning Instruction

Digital positioner
Hide thumbs Also See for PositionMaster EDP300:
Table of Contents

Advertisement

2.3.2

Operation with flammable gas

Observe the following points when operating a device with
flammable gases:
— The device must be used in accordance with the
specifications in the relevant certificate.
— Only the design with the "Intrinsic Safety" type of
protection has been approved for operation with natural
gas. The pneumatic outputs must be vented in non-Ex
areas.
— The maximum ambient temperature must not exceed
60 °C (140 °F).
— During operation with flammable gases in type of
protection "Ex n", the device may only be operated with
approved cable glands.
— During operation with flammable gases, the cover cap for
the air outlets can be removed, and the air outlets can be
tubed separately. Both pipes may not be joined in one
pipe.
Use in areas with combustible dust
Observe the following points when operating a device with
combustible dust:
— To prevent loss of type of protection, the housing may not
be opened.
— Only use cable glands which are approved for the type of
protection and correspond to IP rating ≥ IP 6X.
— Avoid hazardous propagating brush discharge.
2.3.3

Operation in temperature class T6

During operation in temperature class T6, when the equipment
is partially or fully depressurized, ensure that there is no
possibility of a hazardous atmosphere getting into the
pneumatic system or that any hazardous atmosphere is
removed prior to compression by taking suitable action.
When commissioning in temperature class T6, flush the
pneumatic system with 1.4 (+/- 0.1) bar until all traces of any
explosive mixture have been removed (at least 5 minutes).
Ventilate and evacuate the EDP300 fully several times.
6 CI/EDP300-EN Rev. C | PositionMaster EDP300
2.4

ATEX and IECEx temperature data

2.4.1

Type of protection Ex i, intrinsic safety

Temperature
Ambient temperature
class
T4
-40 ... 85 °C (-40 ... 185 °F)
T6
-40 ... 40 °C (-40 ... 104 °F)
2.4.2

Type of protection Ex n - non-sparking

Temperature
Ambient temperature
class
T4
-40 ... 80 °C (-40 ... 176 °F)
T6
-40 ... 40 °C (-40 ... 104 °F)
2.5

ATEX und IECEx electrical data

2.5.1
Type of protection Ex i, intrinsic safety
Basic device
Signal circuit (AI)
Terminals
Temperature class T1 – T4 Temperature class T6
U
= 30 V
i
I
= 320 mA
i
P
= 1.1 W
i
C
= 6.5 nF without pressure option; 8.8 nF with pressure option
i
L
= negligibly small
i
Digital input (DI)
Terminals
Temperature class T1 – T4 Temperature class T6
U
= 30 V
i
P
= 500 mW
i
C
= 4.2 nF
i
L
= negligibly small
i
Digital output (DO)
Terminals
Temperature class T1 – T4 Temperature class T6
U
= 30 V
i
P
= 500 mW
i
C
= 4.2 nF
i
L
= negligibly small
i
Surface temperature
100 °C (212 °F)
55° C (131 °F)
Surface temperature
100 °C (212 °F)
55° C (131 °F)
+11 / -12
U
= 28 V
i
I
= 320 mA
i
P
= 0.8 W
i
+81 / -82
U
= 28 V
i
P
= 400 mW
i
+83 / -84
U
= 28 V
i
P
= 400 mW
i