ABB PositionMaster EDP300 Commissioning Instruction page 10

Digital positioner
Hide thumbs Also See for PositionMaster EDP300:
Table of Contents

Advertisement

Option modules
Module for the emergency shutdown function
Terminals
Temperature class T1 – T6
U
= 30 V
i
P
= 1 W
i
C
= 5.3 nF
i
L
= negligibly small
i
Module for analog feedback (AO)
Terminals
Temperature class T1 – T4 Temperature class T6
U
= 30 V
i
I
= 320 mA
i
P
= 1 W
i
C
= 11.3 nF
i
L
= 150 μH
i
Module for universal input (UAI)
Terminals
Temperature class T1 – T4 Temperature class T6
U
= 30 V
i
I
= 320 mA
i
P
= 1 W
i
C
= 11.3 nF
i
L
= 150 μH
i
Module for digital feedback (SW1 / SW2)
Terminals
Temperature class T1 – T4 Temperature class T6
Per output:
U
= 30 V
i
P
= 0.5 W
i
I
= 250 mA
i
C
= 2.2 nF per output
i
L
= negligibly small
i
Limit switch (Limit 1 / Limit 2)
Limit monitor with proximity switch
Terminals
Temperature class T1 – T4 Temperature class T6
-25 ... 85 °C
1) No IECEx approval
Change from two to one column
10 CI/EDP300-EN Rev. C | PositionMaster EDP300
+85 / -86
+31 / -32
U
= 28 V
i
I
= 320 mA
i
P
= 0.8 W
i
+21 / -22
U
= 28 V
i
I
= 320 mA
i
P
= 0.8 W
i
SW 1: +41 / -42
SW 2: +51 / -52
Per output:
U
= 28 V
i
P
= 0.4 W
i
1)
Limit 1: +51 / -52
Limit 2: +41 / -42
-25°C ... 40°C

Advertisement

Table of Contents
loading

Table of Contents