6.4.2
Electrical connection to the EDP300 remote sensor
Fig. 20: Electrical connection to the EDP300 remote sensor
A Basic device B Options
1 Position sensor
2 Limit monitor with proximity switches (option) 3 Limit monitor with microswitches (option)
Change from one to two columns
Connections for inputs and outputs
Terminal
Function / comments
1 / 2 / 3
EDP300 Control Unit
+51 / -52
Limit switch Limit 1 with proximity switch
(optional)
+41 / -42
Limit switch Limit 2 with proximity switch
(optional)
51 / 52 / 53
Limit switch Limit 1 with microswitch
(optional)
41 / 42 / 43
Limit switch Limit 2 with microswitch
(optional)
A
1
1
2
3
B
2
Limit 1
Limit 1 Limit 2
+51 -52 +41 -42
51 52 53
6.4.3
Electrical data for inputs and outputs
NOTICE
When using the device in potentially explosive atmospheres,
note the additional data in chapter "Use in potentially
explosive atmospheres according to ATEX and IECEx" on
page 5 and in chapter "Use in potentially explosive
atmospheres in accordance with FM and CSA" on page 8 !
Set point signal analog (two-wire technology)
Terminals
Nominal operating range
Limit values
Starting at
Load voltage
Impedance
Digital input DI
Terminals
Supply voltage
Input "logical 0"
Input "logical 1"
Input Current
Digital output DO
Terminals
Supply voltage
Switching state logical
Direction of action
3
Limit 2
41 42 43
M10949
+11 / -12
4 ... 20 mA
Maximum: 50 mA (overload)
Minimum: 3.6 mA
3.8 mA
9.7 V at 20 mA
485 Ω at 20 mA
+81 / -82
24 V DC (12 ... 30 V DC)
0 ... 5 V DC
11 ... 30 V DC
Maximum 4 mA
+83 / -84
5 ... 30 V DC
(Control circuit in accordance with DIN
19234/NAMUR)
"0": Current > 0,35 mA ... < 1,2 mA
"1": Current > 2,1 mA
standard logical "0" or logical "1"
(configurable)
PositionMaster EDP300 | CI/EDP300-EN Rev. C 19