Explosion protection
The values indicated here have been taken out of the respective approval cer-
tificates.
!
Always observe the specifications and supplements in the certificates (see
WARNING
chapter "Certificates" starting on page 38).
FM J.I. 3005029
Intrinsically safe
CL I, Div. 1, Grp. A-B-C-D
CL II, Div. 1, Grp. E-F-G
CL III, Div. 1
Non-incendive
Suitable for use in Div. 2 environment
CSA Certification
Intrinsically safe; Enclosure 4X; T4, max. 85°C
CL I, Div. 1, Grp. A-B-C-D
CL II, Div. 1, Grp. E-F-G
CL III, Div. 1
Non-incendive; Enclosure 4X, max. 85°C
CL I, Div. 2, Grp. A-B-C-D
CL II, Div. 2, Grp. E-F-G
CL III
ATEX
Examination certificate
Type:
Device class:
Temperature class:
Perm. ambient temp.:
ATEX
Examination certificate
Type:
Device class:
Temperature class:
Perm. ambient temp.:
IECEx
Examination certificate
Type:
Temperature class:
Perm. ambient temp.:
41/18-79 EN
(3610, 3611)
1052414
II 2G EEx ib II C T6
TÜV 98 ATEX 1370 X
Intrinsically safe
II 2G (EEx ib IIC)
T4, T5, T6
T4: -40 °C ≤ T
≤ 85 °C
amb
T5: -40 °C ≤ T
≤ 50 °C
amb
T6: -40 °C ≤ T
≤ 35 °C
amb
II 3G EEx n A II T6
TÜV 02 ATEX 1943 X
Explosion-proof (Zone 2)
II 3G (EEx n A II)
T4, T5, T6
T4: -40 °C ≤ T
≤ 85 °C
amb
T5: -40 °C ≤ T
≤ 65 °C
amb
T6: -40 °C ≤ T
≤ 50 °C
amb
Ex ib IIC T6
IECEx TUN 04.0015X, Issue No.: 0
Intrinsically safe
T4, T5, T6
T4: -40 °C < T
< 85 °C
amb
T5: -40 °C < T
< 50 °C
amb
T6: -40 °C < T
< 35 °C
amb
Electro-pneumatic positioner TZIDC